Datasheet
dbl_bus_asi.pdfIssue24.03.2017 · Klaus Faber AG · Lebacher Straße 152 – 156 · 66113 Saarbrücken · Germany · Phone +49 681 9711-0 · Fax -289
FACAB bus cable AS-Interface
conductor material: tinned copper
conductor construction: fine stranded, class 5
flame retardant: VDE 0482-332-1-2/IEC 60332-1-2
maximum temperature at
conductor:
85 °C
max. operating temperature,
fixed:
-40 - +85 °C
temperature, moved/during
installation:
-30 - +85 °C
bending radius, fixed
installation:
3 x DA
bending radius, moved
application:
6 x DA
nominal voltage U: 300 V
test voltage: 2 kV
core identification: colours acc. VDE 0293 (HD308)
Application: As field bus cable for the lowest level (binary sensors and actuators). The cable is suitable for fixed laying
and flexible use indoors.
Additional information: Versions with PUR sheath contain max. 0,5% 2-(2H-benzotriazol-2-yl)-4,6-ditertpentylphenol
(CAS: 25973-55-1) REACH SVHC as UV-absorber.
The products and information presented here are for technical calculation only. They are subject to technical progress and in no way represent the
ability of shipment. Outer diameters are approximately.
Table: Technical characteristics FACAB AS-Interface BUS
p/n part name R
l.
[Ω/km]
b
.
[mm]
h
.
[mm]
F
zv.
[N]
Cu
.
[kg/km]
G
.
[kg/km]
100568 FACAB AS-Interface BUS
Gummi 02X1,5 GE
13,7 10 4 29 57
100569 FACAB AS-Interface BUS
Gummi 02X1,5 SW
13,7 10 4 29 57
101550 FACAB AS-Interface BUS
Gummi 02X2,5 GE
7,98 48 84
100570 FACAB AS-Interface BUS
TPE 02X1,5 GE
13,7 10 4 50 29 57
100571 FACAB AS-Interface BUS
TPE 02X1,5 SW
13,7 10 4 50 29 57
101025 FACAB AS-Interface BUS
PUR 02X1,5 GE
13,7 10 4 50 29 57
101498 FACAB AS-Interface BUS
PUR 02X1,5 SW
29 57