Data Sheet

dbl_bus_asi.pdfIssue23.11.2018 · Klaus Faber AG · Lebacher Straße 152 – 156 · 66113 Saarbrücken · Germany · Phone +49 681 9711-0 · Fax -289
FABER® bus cable AS-Interface
Conductor material: tinned copper
Conductor class: class 5 = fine stranded
Flame-retardant: VDE 0482-332-1-2/IEC 60332-1-2
Maximum permitted
conductor temperature:
85 °C
Permitted outer cable
temperature, fixed:
-40 - +85 °C
Permitted outer cable
temperature, in motion/
during installation:
-30 - +85 °C
Bending radius, fixed
installation:
3 x DA
Bending radius, moving
application:
6 x DA
peak operating voltage: 300 V
Test voltage: 2 kV
Core identification: colours acc. to VDE 0293 (HD308)
Application: As field bus cable for the lowest level (binary sensors and actuators). The cable is suitable for fixed laying
and flexible use indoors.
Additional information: Versions with PUR sheath contain max. 0,5% 2-(2H-benzotriazol-2-yl)-4,6-ditertpentylphenol
(CAS: 25973-55-1) REACH SVHC as UV-absorber.
The products and information presented here are for technical calculation only. They are subject to technical progress and in no way represent the
ability of shipment. Outer diameters are approximately.
Table: Technical characteristics FABER® AS-Interface BUS
p/n part name R
l.
[Ω/km]
b
.
[mm]
h
.
[mm]
F
zv.
[N]
Cu
.
[kg/km]
G
.
[kg/km]
100568 FABER® AS-Interface BUS
Gummi 02X1,5 GE
13,7 10 4 29 57
100569 FABER® AS-Interface BUS
Gummi 02X1,5 SW
13,7 10 4 29 57
101550 FABER® AS-Interface BUS
Gummi 02X2,5 GE
7,98 9,7 4 48 84
100570 FABER® AS-Interface BUS
TPE 02X1,5 GE
13,7 10 4 50 29 57
100571 FABER® AS-Interface BUS
TPE 02X1,5 SW
13,7 10 4 50 29 57
101025 FABER® AS-Interface BUS
PUR 02X1,5 GE
13,7 10 4 50 29 57

Summary of content (2 pages)