Datasheet

34
ODT
External module
INT2
Internal sensor
DIMENSIONS (mm)
WIRING DIAGRAM (mm)
T2
TST24
Phase imbalance
or phase loss
Phase sequence
Overtemperature
Temperature
variation
PROTECTION
FUNCTIONS T2
PROTECTION
FUNCTIONS TST24
Temperature
variation
MODELS
T2 TST24 ODT2 INT2
Nominal voltage of the line to
be monitored (± 15%)
- 3 x 400 V - -
Voltage supply (±15%)
230 Vac
(Aux)
24 Vac, dc
(Aux)
24 Vac, dc
(Aux)
--
Code
12051 12052 12090 12037 12036
CHARACTERISTICS
Nominal frequency 50/60 Hz
Control range
Maximum temperature
from 40˚C to 55˚C.
Maximum temperature
from -5˚C to 5˚C.
Phase loss: with resistive loads it trips when a
phase loss occurs. With three-phase motors it trips
if the voltage regenerated by the motor is lower than
60% of the main voltage. Phase imbalance > 40%.
Maximum temperature setting from 40 ºC a 55 ºC.
Minimum temperature setting from -5 ºC a 5 ºC.
Hysteresis
2˚C
PTC sensor: min/max cold resist
- Trip resist
- 100Ω / 1500Ω - 2300Ω
Trip time delay - < 0,1 s
Reset mode Automatic
Signalling LED’s
2 LED’s: ON +
3 LED’s: ON + +
Output contacts
1 relay with 1 change
over NO - NC
1 relay NO-NC (
) - 1 relay NO-NC (
)
Switching power
T2: I
th
: 5A; AC15 - 250V - 2A; DC13 - 30V - 2A TST24: I
th
: 5A; AC15 - 250V - 2A;
DC13 - 30V - 2A; DC13 - 115V - 0,2A
Maximum terminal section /
screw torque
2,5 mm
2
, No. 22 - 12AWG / 20Ncm, 1.8 LB - IN
Power consumption 7,5 VA (230 Vac) - 11 VA (400 Vac)
Protection degree / weight IP20 / 0,12 kg IP20 / 0,13 kg
Storage / operation temperature
-30°C +70°C / -15°C +60°C
22,5 72,6
100
22,4
61,5
80
WORK LOGIC
TST-24T
Controls the temperature of the motor room (relay + external
module OD-T2) or the temperature inside the switchboards where
there is no motor room (relay + internal sensor IN-T2).
Designed according to the EN 81-1 standard and complying with
the European Union Directive for Lifts (95/16/CE).
• Two adjustable temperature thresholds.
Protection relay against variations of the ambient temperature
(min/max), overtemperature of the motor, phase sequence and
phase imbalance or phase loss.
• DIN rail mounting.
• Visual indication of trip cause.
To Protect 3-phase devices.
Suitable for Motors with built-in PTC sensors in applications such
as elevators, cranes, hoists and similar installations.
• Sensitive to incorrect phase sequence.
• Monitoring of short circuit and broken wire in PTC circuit.
TEMPERATURE CONTROL
PHASE AND TEMPERATURE (PTC) RELAY
Ø 22,5
Ø 30,0
11,3 20,0
1 = 2 m
Tripped
or Us=0
Normal
Tripped
or Us=0
Normal
Temperature
Relay
Tmax
Tmin
Aux.
Supply
contact
11-14
contact
11-12
RST
PTC
ODT / INT tº
24 Vac/dc
Aux. Supply
T
min
T
max
RELAY 11-14
RELAY 21-22
RST RST
T
RSRTS
T-L3
S-L2
R-L1
M
3
Aux Supply
24 Vac/dc
K1
T-L3
S-L2
R-L1
M
K1
N
T TST
14
11
PHASE and TEMPERATURE control relays (Lifts)
www.fanox.com fanox@fanox.com Tlf. +34 94 471 14 09 Fax +34 94 471 05 92