Datasheet

21
ST-D MT
• Self-powered by the voltage to be monitored (S, ST and ST-D).
• Visual indication of tripping cause.
• DIN rail mounting.
Phase and temperature relay Lift temperature control relay Thermistor protection relay
• To protect 3-phase devices
Suitable for motors with built-in PTC sensors in
applications such as elevators, cranes, hoists and
similar installations.
• Sensitive to incorrect phase sequence.
Monitoring of short-circuit and broken wire in
PTC circuit.
Two output relays, one for phase imbalance,
phase loss and phase sequence and the other for
over temperature.
Controls the temperature of the lift motor room
(relay + external module ODT2) or the temperature
inside the switchboard for those lifts without motor
room (relay + internal sensor INT2).
Designed according to the EN 81-1 standard and
complying with the European Union Directive for
Lifts (95/16/CE).
• Two adjustable temperature thresholds.
Controls the temperature by the use of thermistors
(PTC sensors)
Detects short-circuit
(< 25Ω)
and breakage in the
circuit of sensors.
Protects the motors against over temperature
caused by excess ambient temperature,
insufficient ventilation or cooling, etc.
• Applicable in transformers and other machines.
MT2
230 Vac ( Aux.supply)
12039
50/60 Hz
According to the PTC installed
-
50/60 Hz
Maximum temperature setting from 40°C to 55°C
Minimum temperature setting from -5°C to 5°C
2°C
50/60 Hz
-
100Ω / 1500Ω - 2300Ω
< 0,1 s
Automatic
3 LED’s: ON + +
2 relays ( + ) with 1 NO
I
th
: 5A; AC15 - 250V - 2A; DC13 - 30V - 2A
2,5 mm
2
, No. 22 - 12AWG / 20Ncm, 1.8 LB - IN
7,5 VA (230 Vac) - 11 VA (400 Vac)
IP20 / 0,13 kg
-30°C +70°C / -15°C +60°C
-
-
Automatic
2 LED’s: ON +
1 relay with 1 change over NO - NC
I
th
: 5A; AC15 - 250V - 2A; DC13 - 30V - 2A
2,5 mm
2
, No. 22 - 12AWG / 20Ncm, 1.8 LB - IN
5 VA (230 Vac) - 0,5 W (24 Vdc)
IP20 / 0,11 kg
-30°C +70°C / -15°C +60°C
25Ω / 1500Ω - 3600Ω. Reset1800Ω
< 0,1s
Automatic
3 LED’s: ON + +
1 relay with 1 NO + 1 NC
I
th
: 5A; AC15 - 250V - 2A; DC13 - 30V - 2A
2,5 mm
2
, No. 22 - 12AWG / 20Ncm, 1.8 LB - IN
6 VA (230 Vac)
IP20 / 0,12 kg
-30°C +70°C / -15°C +60°C
Phase loss: with resistive loads it trips when a phase loss occurs. With
three-phase motors it trips if the voltage regenerated by the motor
is lower than 60% of the main voltage. Phase inbalance > 40%
Disparado
o Us=0
Normal
RST RTS RST
PTC
RELÉS
3
RST
11-14
21-24
T
RS
+
t
o
Disparado
o Us=0
12
11
14 12
11
14
Normal
contacto
11-14
Tensión
auxiliar
Tmáx
Relé
Tmín
Temperatura
contacto
11-12
PTC Ω
0 Ω
30 s30 s
+
t
o
Normal
9597
9698
9597
9698
ST2-D ST4-D
3 x 230 V 3 x 400 V
Self-powered (3-phase)
12002 12013
T2 ODT2 INT2
––
230 Vac (Aux) 24 Vac, dc
12051 12052 12037 12036
+
+
ODT2
External module
T2
INT2
Internal sensor
T
RELAY
Tripped
or Us=0
Tripped
or Us=0
Tripped
or Us=0
RELAYS
contact
11-14
contact
11-14
ingles interior 2008:ingles interior 2005 13/5/08 17:06 Página 21

Summary of content (1 pages)