Submittal Sheet
Dimensions & Airflow
Clearance of 8” (203 mm) on the bottom of the unit is recommended for removal of core. All units feature three
foot plug-in power cord with 3-prong plug.
Ventilation Performance
in.wg. (Pa) 0.2 (50) 0.4 (100) 0.6 (150) 0.8 (200)
cfm (L/s) cfm (L/s) cfm (L/s) cfm (L/s)
Net supply airow 134 (63) 112 (53) 88 (42) 61 (29)
Gross supply airow 139 (65) 116 (55) 92 (43) 64 (30)
Gross exhaust airow 140 (66) 122 (58) 104 (49) 86 (41)
Energy performance
Heating
Supply temperature Net airow Consumed power
Sensible recovery
efciency
Apparent sensible
effectiveness
Latent recovery/moisture
transfer
F C cfm L/s W % % -
32 0 60 28 66 65 77 0.00
32 0 86 41 96 64 76 0.01
32 0 117 55 148 60 71 0.01
-13 -25 65 31 63 56 81 0.00
United States10048IndustrialBlvd.•Lenexa,KS66215•1.800.747.1762•www.fantech.net
Canada50KanalaktWay•Bouctouche,NBE4S3M5•1.800.565.3548•www.fantech.net
Fantech, reserves the right to modify, at any time and without notice, any or all of its products’ features, designs,
components and specifications to maintain their technological leadership position.
fantech
Requirements and standards
• Complies with the UL 1812 requirements regulating the construction and installation of Heat Recovery Ventilators
• Complies with the CSA C22.2 no. 113 Standard applicable to ventilators
• Complies with the CSA F326 requirements regulating the installation of Heat Recovery Ventilators
• Technical data was obtained from published results of test relating to CSA C439 Standards
• HVI certied
Contacts
Submitted by: Date:
Quantity: Model: Project #:
Comments:
Location:
Architect:
Engineer: Contractor:
Distributed by:
0 25 50 75 100 125 150 175
0
0.
2
0.
4
0.
6
0.
8
1
1.
2
1.
4
1.
6
0 12 24 35 47 59 71 83
0
50
100
150
200
300
350
400
250
Reduced speed
Med. Speed
Normal Supply
Normal Exhaust
1
2
3
4
1
2
3
4
Airow (L/s)
Airow (cfm)
Static Pressure (in H
2
O)
Static Pressure (Pa)
fresh air
to inside
fresh air
from outside
stale air
from inside
stale air
to outside
*Drain line on this side. *Drain line on this side.
Model
A B C D
in mm in mm in mm in mm
Fit 120H 31 785 21 531 10
1
/
4
260 1
7
/
8
50
D
C
A
B