ATMO Spec Sheet

Dimensions & Airflow
Clearance of 17” (432 mm) in front of the unit is recommended for removal of core. All units feature three foot
plug-in power cord with 3-prong plug.
Model
A B C D
in mm in mm in mm in mm
ATMO 150E 23
7
/
8
606 29
1
/
2
750 11
11
/
16
423 21
7
/
16
545
fresh air
to inside
fresh air
from outside
stale air
from inside
stale air
to outside
Ventilation Performance
in.wg. (Pa) 0.2 (50) 0.4 (100) 0.6 (150) 0.8 (200) 1.0 (250)
cfm (L/s) cfm (L/s) cfm (L/s) cfm (L/s) cfm (L/s)
Net supply airow 188 (89) 160 (76) 132 (62) 104 (49) 76 (36)
Gross supply airow 190 (90) 162 (77) 132 (62) 106 (50) 78 (37)
Gross exhaust airow 186 (88) 158 (75) 131 (62) 104 (49) 80 (38)
Energy performance
Supply temperature Net airow Consumed Power
Net effectiveness
Sensible Total Recovery Apparent Sensible
1
Latent recovery/
moisture transfer
F C cfm L/s W % % %
Heating
32 0 65 31 50 75 84 0.50
32 0 85 40 60 73 81 0.56
32 0 106 50 76 71 78 0.53
Cooling
-13 -25 65 31 48 60 81 0.47
95 35 64 30 52 60 75 0.60
United States 10048 Industrial Blvd. • Lenexa, KS 66215 • 1.800.747.1762 • www.fantech.net
Canada 50 Kanalakt Way • Bouctouche, NB E4S 3M5 • 1.800.565.3548 • www.fantech.net
Fantech, reserves the right to modify, at any time and without notice, any or all of its products’ features, designs,
components and specifications to maintain their technological leadership position.
Distributed by:
Contacts
Submitted by: Date:
Quantity: Model: Project #:
Comments:
Location:
Architect:
Engineer: Contractor:
Requirements and standards
Complies with the UL 1812 requirements regulating the construction and installation of Heat Recovery Ventilators
Complies with the CSA C22.2 no. 113 Standard applicable to ventilators
Complies with the CSA F326 requirements regulating the installation of Heat Recovery Ventilators
Energy Recovery Core is certied for mold and bacteria resistance
Technical data was obtained from published results of test relating to CSA C439 Standards
AB B
C
D
1
Not an HVI certied value