Dimensions & Airflow
Clearance of 22” (559 mm) in front of the unit is recommended for removal of core. All units feature three foot
plug-in power cord with 3-prong plug.
Model
A B C D
in mm in mm in mm in mm
ATMO 200E 23
7
/
8
606 29
1
/
2
751 16
5
/
8
423 21
7
/
16
546
fresh air
to inside
fresh air
from outside
stale air
from inside
stale air
to outside
Ventilation Performance
in.wg. (Pa) 0.2 (50) 0.4 (100) 0.6 (150) 0.8 (200) 1.0 (250)
cfm (L/s) cfm (L/s) cfm (L/s) cfm (L/s) cfm (L/s)
Net supply airow 233 (110) 201 (95) 167 (79) 132 (62) 97 (46)
Gross supply airow 234 (111) 203 (96) 169 (80) 134 (63) 97 (46)
Gross exhaust airow 229 (108) 197 (93) 165 (78) 131 (62) 63 (44)
Energy performance
United States 10048 Industrial Blvd. • Lenexa, KS 66215 • 1.800.747.1762 • www.fantech.net
Canada 50 Kanalakt Way • Bouctouche, NB E4S 3M5 • 1.800.565.3548 • www.fantech.net
Fantech, reserves the right to modify, at any time and without notice, any or all of its products’ features, designs,
components and specifications to maintain their technological leadership position.
Distributed by:
Contacts
Submitted by: Date:
Quantity: Model: Project #:
Comments:
Location:
Architect:
Engineer: Contractor:
Requirements and standards
• Complies with the UL 1812 requirements regulating the construction and installation of Heat Recovery Ventilators
• Complies with the CSA C22.2 no. 113 Standard applicable to ventilators
• Complies with the CSA F326 requirements regulating the installation of Heat Recovery Ventilators
• Energy Recovery Core is certied for mold and bacteria resistance
• Technical data was obtained from published results of test relating to CSA C439 Standards
AB B
C
D
Supply temperature Net airow Consumed Power
Net effectiveness
Sensible Total Recovery Apparent Sensible
1
Latent recovery/
moisture transfer
F C cfm L/s W % % %
Heating
32 0 67 32 52 75 84 0.72
32 0 86 40 58 73 81 0.70
32 0 107 51 72 71 78 0.67
-13 -25 66 31 45 60 81 0.59
Cooling 95 35 64 30 48 65 80 0.72
1
Not an HVI certied value