Submittal Sheet

Specification Sheet
Rev Date: 030315
ECHO H2800Xi
Commercial Heat Recovery Ventilator - Indoor Unit
Product #: 95749
The Commercial Heat Recovery Ventilation system (HRV) complements
today's tight buildings. Fantech's HRVs are designed to supply air into a
building while exhausting an equal amount of contaminated air to the
outside.
Features
2800 cfm unit
EC Fan motors
Pre-Programmed controller
Built-in Flow Measurement
Electronic Flow Adjustment
Available communication via Modbus and BACnet
Dirty Filter Sensor
Field reversible electrical box
Dual service doors
Push-pull configuration
Specifications
Voltage – 200 - 240V
Phase – 1~
Current – 12.2A
Power rated, per motor – 1300W
MCA 14A
MOP 20A
Operational Temperature – -25/40˚ C (-13/104˚ F)
Weight – 850 lbs (386 kg)
Fans
Two (2) electronically commutated motors. The EC fans operate at high
efficiency levels and offer a great energy-saving potential not only at full
load, but especially at part-load. When operating at part-load, the energy
used is much lower than with an AC motor of equivalent output. Reduced
energy usage guarantees a drop in operating costs.
Heat recovery core
Three (3) aluminum heat recovery cores configured for an efficient cross-
flow ventilation. Core is 23.6” x 23.6” (600 x 600 mm) with a 15.6” (397
mm) depth. Cores are manufactured to withstand extreme temperature
variations.
Defrost
The Heat Recovery ventilation system incorporate a standard supply
fan shutdown defrost. An external recirculation defrost that does not
depressurize the space during the defrost cycle is also available as an
accessory.
Serviceability
Cores, filters and drain pan can be accessed easily from both sides of the
unit from hinged and removable access doors. Cores conveniently slide
out and blowers can be accessed from both side of the HRV from
fastened access panels. Blowers are easily removable by taking off the
access panel. A clearance of 44" (1120 mm) is required to service the
unit.
Cabinet
Double wall construction with 22 gauge galvanized pre-painted steel
corrosion resistant
Insulation
Insulated with 2in. (50 mm) fiberglass with FSK facing for condensation
control.
Controls
Factory installed and pre-programmed controller with remote display for
monitoring and configuring the unit. Available communication via Modbus
and BACnet.
Filters
The air streams are protected by a MERV13 pleated filter on the supply
air and a MERV8 pleated filter on the exhaust air. Filter dimensions are
24" x 24" (610 mm x 610 mm)
Installation
Unit may be suspended by using threaded rod, not supplied, or placed on
a platform. Unit shall be adaptable for easy service of electrical
components.
Specification Sheet
Item #: 422972
Rev Date: 2019-04-08

Summary of content (2 pages)