1 Cut hole in duct and insert flow measuring
station. Make sure that the flow measuring
station’s air direction arrow points in the
direction of the airflow. Secure the flow
measuring station with aluminum foil tape.
2 Before taking the reading, make sure that
the magnehelic gauge is level and at 0.
Refer to the flow measuring station’s
chart to determine your unit’s airflow
velocity.
3 Adjust the “Supply Air Out” damper until
you reach the desired velocity. Follow
steps 1-3 to adjust the “Exhaust Air Out”
damper, if needed.
Measure
here
Minimum
457mm
(18")
Measure
here
Minimum
457mm (18")
• To avoid airflow turbulence and incorrect
readings, the airflow velocity should be
measured on a section of steel ducting.
Reading should also be taken at a minimum
distance of 457 mm (18") from the unit or
elbow. Measurement should also be made
prior to any transition in the duct work so
entire airflow is measured.
Measuring the airflow using station (grid) method