FKD 12 XL Mixed Flow Fan Specification
United States 10048 Industrial Blvd. • Lenexa, KS 66061 • 1.800.747.1762 • www.fantech.net
Canada 50 Kanalakt Way • Bouctouche, NB E4S 3M5 • 1.800.565.3548 • www.fantech.ca
Fantech reserves the right to make technical changes.
For updated documentation please refer to www.fantech.net
Guide Specification
Item #: 450420
Rev Date: 080113
fantech
FKD Series
Inline Centrifugal Fans
Description
A mixed flow centrifugal type exhaust/supply fan for moderate size ventilation applications specifically designed to bridge the transition from centrifugal
to axial. FKD Series fans offer substantially quieter performance and are easier to install than axial arrangements. Fans can be mounted at any angle in
any point along the duct work and straight-through air flow design allows easy installation. Fans can be easily removed from duct work for service. Fan
motors are capable of operating in air stream temperatures of 140
o
F. Motor bearings are a permanently sealed, self lubricating ball type. All fans are
100% speed controllable through a decrease in the voltage by using a solid state or transformer type control. All FKD Series fans are backed by
Fantech’s Three Year Warranty.
Guide Specifications for Model FKD Inline Duct Fans
Supply, exhaust or return air inline fans shall be of the centrifugal, direct driven type.
Construction
Housing
Fan housing shall be constructed of heavy gauge galvanized sheet metal
Fan shall be supplied with externally mounted electrical terminal box with pre-wired terminal strip connections
Motor
Motorized impeller shall be an enclosed external rotor type. Single phase motors (FKD8XL – FKD18) shall be 120 or 230V permanent split
capacitor type
Three phase motors (FKD18XL, FKD20) shall be dual wound for 230V or 440/460V
All motors shall be a permanently sealed self lubricating ball bearing type
Single phase motors shall be equipped with automatic reset thermal overload protection
Three phase motors shall be equipped with internal automatic reset thermal overload switch for interlock with contactor
Motors shall be acceptable for continuous duty
Sufficient service factor shall be provided to ensure long maintenance free operation over maximum load conditions
Wheel
Fan wheel shall be of the mixed flow centrifugal type with a well designed inlet venturi for maximum performance
Motorized impeller shall be both statically and dynamically balanced as one integral unit to provide for vibration free performance
Impellers for models FKD 12XL through FKD18 shall be molded of high impact polypropylene
Impeller for FKD 8XL through FKD 12, FKD 18XL and FKD 20 shall be constructed of aluminum
Performance
Fan air flow and sound performance shall be based on tests conducted in accordance with AMCA Standard 211 and 311 and shall be licensed
to bear the AMCA Certified Ratings label
Code Approval
Fan shall be tested and approved by UL and CSA (or equals) for safety
FKD Series shall be manufactured under the authority of Fantech, Inc., Lenexa, KS.