Spec Sheet

United States 10048 Industrial Blvd. • Lenexa, KS 66215 • 1.800.747.1762 • www.fantech.net
Canada 50 Kanalakt Way • Bouctouche, NB E4S 3M5 • 1.800.565.3548 • www.fantech.net
Systemair reserves the right to modify, at any time and without notice, any or all of its products’ features, designs, compo-
nents and specifications to maintain their technological leadership position.
Dimensions & Airflow
Dimensional information is in inches. Clearance of 12” (305mm) in front of the unit is recommended for removal
of core. All units feature three foot plug-in power cord with 3-prong plug.
Model A B C D
in mm in mm in mm in mm
HERO 120H 23
1
/
4
590 11
1
/
2
291 22
5
/
8
575 24
1
/
4
616
fresh air
to inside
fresh air
from outside
stale air
from inside
stale air
to outside
Ventilation Performance
in. wg. (Pa) 0.1 (25) 0.2 (50) 0.3 (75) 0.4 (100) 0.5 (125) 0.6 (150) 0.7 (175) 0.8 (200)
cfm (L/s) cfm (L/s) cfm (L/s) cfm (L/s) cfm (L/s) cfm (L/s) cfm (L/s) cfm (L/s)
Net supply airow 133 (63) 125 (59) 119 (56) 110 (52) 102 (48) 91 (43) 83 (39) 72 (34)
Net supply airow
with MERV8 lter
115 (54) 108 (51) 102 (48) 96 (45) 90 (42) 84 (40) 77 (36) 70 (33)
Gross supply airow 136 (64) 127 (60) 121 (57) 112 (53) 104 (49) 93 (44) 85 (40) 74 (35)
Gross exhaust airow 136 (64) 127 (60) 121 (57) 112 (53) 104 (49) 93 (44) 85 (40) 74 (35)
Energy performance
Heating
Supply temperature Net airow Consumed power
Sensible recovery
efciency
Ajusted Sensible
recovery efciency
Apparent sensible
effectiveness
Latent recovery/moisture
transfer
O
F
O
C cfm L/s W % % % -
32 0 70 33 60 80 86 89 0.01
32 0 100 47 105 75 83 85 0.01
32 0 117 55 160 70 79 81 0.02
-13 -25 68 32 100 63 67 95 0.05
Distributed by:Contacts
Submitted by: Date:
Quantity: Model: Project #:
Comments:
Location:
Architect:
Engineer: Contractor:
* This product earned the ENERGY STAR® by meeting strict efciency guidelines set by Natural Resources Canada and the US EPA. It meets ENERGY STAR® requirements only when used in
Canada.
Requirements and standards
Complies with the UL 1812 requirements regulating the construction and installation of Heat Recovery Ventilators
Complies with the CSA C22.2 no. 113 Standard applicable to ventilators
Complies with the CSA F326 requirements regulating the installation of Heat Recovery Ventilators
Technical data was obtained from published results of test relating to CSA C439 Standards. This data was optained without the use of the MERV8
supply lter.
HVI certied and ENERGY STAR® qualied*
A
B
D
C
0 20 40 60 80 100 120 140 160
0 9 19 28 37 47 57 66 76
0.0
0.2
0.4
0.6
0.8
1.0
0
50
100
150
200
225
Airow [l/s]
Airow [cfm]
Static Pressure [in.wg]
Static Pressure [Pa]
Reduced Speed
Med Speed
Normal Speed
Normal Speed
with MERV8
lter
3
2
1
1
3
2
4
4
Energy performance results were obtained without the MERV-8 filter installed.