Installation Manual MUAS Series Makeup Air System & Controller Technical / Customer Support: United States Tel.: 800.747.1762 Canada Tel.: 800.565.
Note Warning / Important note Information Technical information Practical tip Warnings Caution TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING: 1. Do not locate outside air inlet near hazardous materials or explosives. 1. Installation work and electrical wiring must be done by a qualified person(s) in accordance with national electric codes, local electric codes, ordinances and regulations, including fire-rated construction codes and standards. 2.
Application The Fantech Exhaust Makeup Air System is a low voltage controlled assembly of components which provides the automatic supply of outdoor air into a building. When controlled by the current sensing Fantech Makeup Air Controller “FMAC”, the system is suitable as compensation for single speed, multi-speed, and variable speed exhaust fans.
Exhaust Makeup Air System Components 8 7 6 5 4 3 1 2 2 Figure 1.
Dimensions MUAS 750 & MUAS 1200 Ø A C B J E D H F G Model A B C D E F H (optional) G J MUAS 750 10 10 30 1/2 7 7/8 26 5/8 85 14 99 8 MUAS 1200 10 10 30 1/2 9 13/16 38 1/2 98 13/16 14 112 13/16 10 Dimensions are in inches.
Makeup Air System Installation Read all instructions before starting installation. Low voltage wiring should be routed the shortest distance possible to avoid unnecessary voltage drop. The current transducer wire shall be a minimum 20 AWG twisted pair. The current transducer and all control wires shall be kept away from high voltage wiring to avoid signal interference. Recommended ambient operating temperature range for the makeup air system is -20oF (28.8oC) to 140oF (60oC).
Makeup Air Controller and System Startup: Prior to beginning the setup and startup procedure, verify that the makeup air system is completely installed and wired, and verify that the compensated exhaust system is completely installed and wired. a. Install a clean panel filter into the makeup air system’s filter cassette. b. Energize the power circuits to; • Makeup air fan. • Transformer. A power indicator and heart pulse LED will illuminate when the FMAC is energized and ready for programming.
Controller Operation and System Wiring When the FMAC's controller receives a signal from the current transducer that the compensated exhaust fan is operating, the FMAC controller's outputs will be activated. The controller will provide a 24VAC signal to power the motorized damper to the open position. The controller will provide a 0-10VDC signal to the makeup air supply fan to operate the fan at a speed proportional to the compensated exhaust fan's speed.
MUAS Control Enclosure 5/16-18 X 5/8 MOUNTING STUDS WALL MOUNTING PLATE NEMA 1 ELECTRICAL ENCLOSURE ELECTRICAL ENCLOSURE BACK PANEL (4)5/16-18 HEX NUT JUNCTION BOX 4X4 (2)#10-16 X 1/2 HWH DRILL SCREW INCLUDED WITH TRANSFORMER TRANSFORMER 50VA CONTROL MODULE ELECTRICAL ENCLOSURE COVER PLATE INCLUDED WITH NEMA ELECTRICAL ENCLOSURE REMOVE THE TWO #10-32 X 1/2 SCREWS FROM THE BACK OF THE MODULE AND MOUNT THE MODULE TO THE ENCLOSURE BACK PANEL USING THE 2 HOLES PROVIDED MAKEUP AIR SYSTEM CONTROL BOX AS
Notes All wiring is by others. Wiring terminations for each component are contained in their respective installation instructions. Placement of components is up to the discretion of the installing contractor. For applications with small current loads (such as less than 2 Amps), wrap the monitored conductor through the sensor aperture several times to increase the current measured by the sensor. Example: Exhaust fan amperage rating of 2 amps. One pass through the CS650-10 aperture V output is approx.
Sensor - Temperature Sensor Installation TEMPERATURE SENSOR INSTALLATION TEMPERATURE SENSOR INSTALLATION 40'' 40'' 1016mm 1016mm RECOMMENDED POSITION RECOMMENDED POSITION TEMPERATURE SENSOR TEMPERATURE SENSOR AIRFLOW AIRFLOW FRONT FRONT DRILL DRILL O1/2''O1/2'' [13mm] [13mm] XX XX DO NOT INSTALL THETHE SENSOR IN AN OR A TRANSITION DO NOT INSTALL SENSOR IN ELBOW AN ELBOW OR A TRANSITION Electrical Connection L1 L2 / N Gnd The heater does not come with a disconnect switch, the power should be
Warranty Five (5) Year Warranty This warranty supersedes all prior warranties DURING ENTIRE WARRANTY PERIOD: Fantech will repair or replace any part which has a factory defect in workmanship or material. Product may need to be returned to the Fantech factory, together with a copy of the bill of sale and identified with RMA number. FOR FACTORY RETURN YOU MUST: • Have a Return Materials Authorization (RMA) number. This may be obtained by calling Fantech either in the USA at 1.800.747.
Notes fantech
Notes fantech
Notes fantech
Fantech reserves the right to make technical changes. For updated documentation please refer to www.fantech.