Brochure

RVF INSTALLED
RVF 4XL
RVF SERIES
EXTERIOR-MOUNT EXHAUST FANS
RVF Series performance is shown with ducted inlet. Per HVI‘s Certified Ratings Program, charted air flow performance has been derated by a factor based on actual test results and
the certified rate at .1 inches WG.
PERFORMANCE DATA
Fan Energy Rated Max.
Static Pressure in Inches W.G.
Max. Duct
Model Star
RPM Volts
Watts
Wattage Range
Amps
0” 0.1” 0.2” 0.4” 0.6” 0.8” 1.0” 1.5”
Ps Dia.
RVF 4 !
3060 115 19 15 – 19 0.17 134 120 112 83 37 0.78” 4”
RVF 4XL
2700 115 92 73 – 92 0.84 193 180 172 154 136 118 91 1.61” 4”
RVF 6
2550 115 92 78 – 93 0.84 242 220 204 177 150 123 68 1.27” 6”
RVF 6XL
3000 115 149 145 – 157 1.46 381 360 346 315 285 258 213 64 1.74” 6”
RVF 8XL
2900 115 151 140 – 155 1.42 435 410 392 348 312 282 235 102 1.82” 8”
United States 1712 Northgate Blvd. • Sarasota, FL. 34234 • 1.800.747.1762 • www.fantech.net
Canada 50 Kanalflakt Way • Bouctouche, NB E4S 3M5 • 1.800.565.3548 • www.fantech.ca
Fantech, reserves the right to modify, at any time and without notice, any or all of its products’ features, designs, components and specifications to maintain their technological leadership position.
Item #: 450483
Rev Date: 082208
AIR PERFORMANCE GRAPHS
Static Pressure (in H
2
0)
Flow Rate (CFM)
0 50 100 150 200 250 300350 400450 500
2.00
1.80
1.60
1.40
1.20
1.00
0.80
0.60
0.40
0.20
0.00
RVF 4
X
L
RVF 8
XL
RVF 6
XL
RVF 6RVF 4
DIMENSIONAL DATA
model A
B C D E
RVF 4
4 10
1
/4 13 6 2
3
/4
RVF 4XL
4 10
1
/4 13 6 2
3
/4
RVF 6
6 10
1
/4 13 6 2
3
/4
RVF 6XL
6 14
1
/4 17 6 2
3
/4
RVF 8XL
8 14
1
/4 17 6 2
3
/4
1
"
D
B
C
E
A
All dimensions in inches.
Duct connection is
1
/8 smaller than duct size.
FIVE
YEAR
WARRANTY
Look for the Energy
Star Rated Models
in Performance