SHR 1504 Installation Manual
4
Power
• Volts 120 VAC
• Amperage
SHR 1504/1505R 1.3 Amps
SHR 2004/2005R 2.1 Amps
SHR 3005R 2.8 Amps
SHR 3205RD 2.5 Amps
• Single Phase
A
B C D
F
E
Dimensions Airflow Path
SHR1504
SHR1505R
280
133
154
320
SHR 3205RD
Fresh Air
From Outside
Stale Air
To Outside
Fresh Air
To Inside
Stale Air
From Inside
3 ft, 3 prong
Power Cord
1/2
II
Drain
SHR 1504, SHR 1505R, SHR 2004, SHR 2005R, SHR 3005R & SHR 3205RD
Heat Recovery Ventilators
Fan Performance Performance Data
SHR 3005R Unit is larger to accommodate 2 heat recovery cores. Electrical box is inside cabinet.
Measurements
SHR 1504 SHR 1505 SHR 2004 SHR 2005R SHR 3005R SHR 3205RD
A 56mm (2
1
/
4
") 56mm (2
1
/
4
") 56mm (2
1
/
4
") 56mm (2
1
/
4
") 56mm (2
1
/
4
") 56mm (2
1
/
4
")
B 596mm (23
1
/
2
") 596mm (23
1
/
2
") 707mm (27
7
/
8
") 707mm (27
7
/
8
") 1292mm (50
7
/
8
") 707mm (27
7
/
8
")
C 67mm (2
5
/
8
") 67mm (2
5
/
8
") 67mm (2
5
/
8
") 67mm (2
5
/
8
") 56mm (2
1
/
4
") 71mm (2
3
/
4
")
D 441mm (17
3
/
8
") 441mm (17
3
/
8
") 441mm (17
3
/
8
") 441mm (17
3
/
8
") 441mm (17
3
/
8
") 638mm (25
1
/
8
")
E 413mm (16
1
/
8
") 441mm (17
3
/
8
") 520mm (20
1
/
2
") 520mm (20
1
/
2
") 562mm (22
1
/
8
") 520mm (20
1
/
2
")
F 152mm (6") 152mm (6") 152mm (6") 152mm (6") 152mm (6") 203mm (8")
Apparent
Sensible
Effectiveness at
-25°C (-13°F)
Apparent
Sensible
Effectiveness at
0°C (32°F)
Power
Consumed
Watts
at 0°C (32°F)
Model
SHR 1504 73% @31 L/s (65 CFM) 77% @32 L/s (68 CFM) 72 @31 L/s (65 CFM)
SHR 1505R 73% @31 L/s (65 CFM) 77% @32 L/s (68 CFM) 72 @31 L/s (65 CFM)
SHR 2004 77% @31 L/s (65 CFM) 79% @61 L/s (129 CFM)
108 @31 L/s (65 CFM)
SHR 2005R 77% @31 L/s (65 CFM) 81% @59 L/s (126 CFM)
108 @31 L/s (65 CFM)
SHR 3005R 92% @55 L/s (117 CFM) 91% @57 L/s (121 CFM)
212 @55 L/s (117 CFM)
SHR 3205RD 77% @56 L/s (118 CFM) 79% @58 L/s (123 CFM)
136 @56 L/s (118 CFM)
TECHNICAL DATA