Oil & Gas Wireless Enabled Monitoring System 11
Installer’s Guide
Pre-installation iTLM-1 Depth Calibration
Before installing the iTLM-1 sensor device on a tank, perform the iTLM-1 depth
calibration procedure. See the Section entitled, “iTLM-1 Depth Calibration” on
page 42 of Chapter 3, “WEMS Software”, for details.
Installation Instructions
When installing any of the iMonitoring wireless devices care must be taken to
guarantee that the wireless devices are installed and provisioned in its intended
configuration and the installation guarantees compliance to regulatory and safety
requirements.
Monitor Installation Instructions
The following instructions are to be performed for each monitor (iEFM, iTLM-1,
and iWPM-T) at installation.
1 Remove the monitor packing carton.
2 Remove the reset button access screw (Phillips head) on the bottom
of the unit, and using a non-metalic probe, press and hold the reset
button momentarily to bring the unit out of the sleep mode. Replace
the screw.
3 Install the antenna onto the SMA connector on the monitor.
4 On the iEFM and iWPM-T, install the temperature sensor on the monitor.
5 Using the WEMS Software module PocketConfig, enter the monitor’s
unique serial number and press the Configure button to enter the
unit-level configuration. Refer to Chapter 3‚ “WEMS Software,” on
page 13 for more information on using PocketConfig.
6 In the resulting Config tab screen, enter the following information: