Submittal Sheet

FEATURES
n
Proven pressure switch input
n
Combustion fan output
n
24/120/240 VAC hot surface ignitor models available
n
ASME CSD-1 compatible models available (consult factory)
n
Pre-purge and lockout indicator outputs
n
Diagnostic LED
n
Multiple trials for ignition
n
Thermostat, pushbutton or remote reset
n
Remote diagnostic LED
n
Remote flame sensor option
n
Flame current test pins
APPLICATIONS
Commercial and industrial appliances with combustion
chambers in excess of 400K BTU. Applications requiring
CSD-1 certification.
DESCRIPTION
The Series 35-67 is a hot surface ignition system in which
the ignition source is proven to be capable of ignition prior to
the gas valve being opened and is suitable for appliances over
400K BTU. Models compatible to the requirements of ASME
standard CSD-1 are available.
The microprocessor circuit design provides precise, repeatable
timing sequences for ignition times and purge times (pre-, inter-,
and post-) as well as multiple tries for ignition. The control also
continuously monitors the pressure switch, thermostat and main
burner flame to ensure safe system operation. On-board diagnostics
with LED output provide assistance with troubleshooting to ensure
safe and efficient burner operation.
Agency Certifications
Design certified by CSA International to CAN C22.2 #199-M89 and
ANSI Z21.20 for Automatic Ignition Systems, including UL1998
Software Review.
SERIES 35-67
24 VAC Proven Hot Surface Ignition Control
with Combustion Blower Relay Microprocessor Based
SPECIFICATIONS
www.fenwalcontrols.com 1-800-FENWAL-1
Series 35-67, 24 VAC Hot Surface Ignition Control Page 1
INPUT VOLTAGES
Control
Line
Thermostat
Pressure Switch
Hot Surface Element
Output Ratings
Inducer Fan
Hot Surface Element
Gas Valve Rating
Lockout & Pre-Purge Indicators
Operating Temperature
Flame Sensitivity
Flame Failure Response Time
Types of Gas
Ignitor
Enclosure
Moisture Resistance
Size with enclosure
Weight
DESCRIPTION
18 to 30 VAC, 400mA max
(not including gas valve)
24/120/240 VAC (L1 & L2 only,
voltage depends on model)
18 to 30 VAC 30mA max (incl. Gas Valve)
18 to 30 VAC 25mA max
24/120/240 VAC 5A max
Relay: 15A max or 1/3HP @ 120 or 240 VAC
5.0A max @ 24, 120 or 240 VAC
5.0A max @ 24 VAC
1.0A max @ 24 VAC
-40ºF to +165ºF (-40ºC to +73ºC)
4.0mA minimum
0.8 seconds max
Natural, LP, or manufactured
24 VAC, 120 VAC, or 240 VAC
mini-ignitors and silicon carbide ignitors
depending on model
Gray (Noryl N-190)
Conformal coated to operate non-condensing
to 95% R.H. Care must be taken to protect
module from direct exposure to water
See Figures 6 & 7
8oz including options and cover
®
35.67.02

Summary of content (8 pages)