PROPERLY SETTING THE AIRFLOW ADJUSTMENTS ON THE POWER VENTER AND DRAFT CONTROL
1.  Set the adjustment damper in the SWG venter to its full open position.
2.  Start with no weights on the chain hanger of the MG-1 draft control.
3.  Follow the appliance manufacturer's procedures for starting the heating appliance. Then adjust the 
thermostat to call for HEAT.
4.  After the system has operated for at least 10 minutes to stabilize ue gas temperatures, check for 
negative draft or up-draft at the heating appliance outlet. Use a draft gauge, velocity meter or match 
test procedure.
5.  Loosen the damper locking screw on the underside of the SWG outer pipe and rotate the adjustment 
damper closed to obtain the minimum air ow required to maintain draft. Then increase air ow slightly 
(10% over minimum air ow rate) to ensure proper venting. If using a draft gauge, draft settings should 
typically be -0.02" of water column draft at the appliance outlet. (Check equipment requirement.)
6.  Observe the position of the gate on the draft control. It should be set so that during normal operation the 
gate is in the midpoint of its swing. This will be approximately 30º - 45º from vertical.
7.  When rst setting up the system the gate on the control will probably be fully open. Add washer weights 
to the chain hanger until the gate stabilizes at the midpoint of its swing.
8.  Changing the weight on the draft control will aect the system draft, therefore repeat steps 5 through 7 
as necessary until proper draft is obtained and the draft control gate is in the proper position.
9.  Tighten the damper locking screw on the SWG to prevent it from moving during operation and secure the 
washer weights on the draft control with the provided screw and nut.
Figure 13
WHILE ADJUSTING THE SYSTEM AIRFLOW, TWO THINGS ARE ESSENTIAL
1.  The appliance burner must operate for at least 10 minutes prior to setting the draft to stabilize ue gas 
temperatures.
2.  An analysis of the ue gases is necessary to determine the percentage of CO
2
 and check for the 
presence of CO. Refer to the local gas company for the proper CO
2
 readings and allowable CO levels.
Refer to the General Installation Inspection section to check for negative pressure problems in the building. 
If sucient combustion air for the burner is not provided, a ow reversal during the o cycle could occur 
within the venting system. This may cause combustion problems as well as condensation that could block 
the air pressure sensing tube. It may also contribute to premature motor failure. Combustion, and/or makeup 
air, should be supplied from outside the structure and the air inlet should be on the same wall as the power 
venter discharge. For example, tightly constructed homes and homes retrotted from electric heated systems 
are more likely to experience combustion and/or makeup air problems. For further information consult Form 
#4199, “The Field Report - Eects of Insucient Combustion Air” available from Field Controls.
or removing the washer-like weights (supplied with the 
control) to or from the weight holder chain assembly. After 
the control is adjusted, its action will be entirely automatic, 
the gate will open or close by itself to correct for changes 
in the draft. The control MUST be adjusted to the desired 
draft setting by adding or removing the washer-type 
weights supported by the two chains on the side of the 
draft control. (See Figure 13) DO NOT move the weight 
attached directly to the gate, this is used only for balancing 
at the factory.