Overview of Primary Product
page 8
AIR FLOW ADJUSTMENTS
In order to obtain proper system draft, the power venter has an air ow adjustment 
damper built in. When used in a system with a barometric draft control, this damper 
should be used to make coarse draft adjustments, while the barometric should be used 
for  ner adjustments. Loosen the locking screw on the air  ow adjustment damper 
on the outer pipe of the power venter. (See Figure 11) Adjust the damper to the full 
open position. Follow appliance manufacturer’s procedures for starting the heating 
appliance. Then adjust the thermostat to call for “Heat”. After the system has operated 
for several minutes to stabilize  ue gas temperatures, check for negative draft or up-
draft at the heating appliance outlet or air  ow into the draft hood. Use a draft gauge, 
velocity meter or match test procedure. Adjust the adjustment damper closed to obtain 
the minimum air  ow required to maintain draft. Then increase air  ow slightly (10% 
over minimum air  ow rate) to ensure proper venting. For oil- red or gas- red power 
burners, adjust draft to proper over- red draft.
If proper draft has been established, tighten the adjustment locking screw. For gas- red systems, shut o 
thermostat and check for residual heat spilling from draft hood. If this occurs, a post purge timer may be 
required. If so, use a Field Controls PPC-5 Electronic Post Purge or a Control Kit which includes one. Before 
installing, refer to the General Installation Inspection to check for negative pressure problems in the building. 
If su  cient combustion air for the burner is not provided, a  ow reversal during the o  cycle could occur 
within the venting system. This may cause combustion problems as well as condensation that could block the 
air pressure sensing tube. It may also contribute to premature motor failure. Combustion, and/or make-up air, 
should be supplied from outside the structure and the air inlet should be on the same wall as the power venter 
discharge. For example, tightly constructed homes and homes retro tted from electric heated systems are 
more likely to experience combustion and/or make-up air problems. For further information consult “The Field 
Report–E ects of insu  cient combustion air on draft and heating systems”. Refer to the appropriate control 
kit installation instructions for pressure switch adjustment procedure and system checkout procedures before 
operating continuously.
NOTE: After proper venting has been established, it is recommended that a combustion test on gas and oil 
units, a check for CO levels on gas units, and a smoke test on oil systems be performed to ensure maximum 
burner e  ciency. Oil burner air adjustments should be set at a zero to a trace smoke at the highest or 
recommended CO
2
% setting set by heating equipment manufacturer.
GENERAL INSTALLATION INSPECTION
Recommended procedures for safety inspection of an appliance in accordance with the National Fuel Gas 
Code ANSI Z223.1. The following procedure will help evaluate the venting system. It is intended as a guide 
to aid in determining that the venting system is properly installed and is in a safe condition for continuous 
use. This procedure should be recognized as a generalized procedure which cannot anticipate all situations. 
Accordingly, in some cases, deviation from this procedure may be necessary to determine safe operation of 
the equipment. If it is determined that a condition exists which could result in unsafe operation, the appliance 
should be shut o  and the owner advised of the unsafe condition. Corrections must be made before the 
appliance is put into continuous operation. The following steps should be followed in making a safety 
inspection.
1.  Visually inspect the venting system for proper size and determine that there is no  ue gas spillage, 
blockage, restriction, leakage, corrosion or other de ciency which could cause an unsafe operation.
2.  Insofar as practical, close all building doors,  replace dampers, windows and all doors in area in which 
the appliance is located. Turn on clothes dryers, any exhaust fans, such as range hoods and bathroom 
exhausters so they operate at maximum speed. Do not operate a summer exhaust fan. If, after completing 
Steps 3 through 7 it is believed su  cient combustion air is not available, refer to the National Fuel Gas 
Code ANSI Z223.1, or any applicable local codes for guidance.
3.  Place in operation the appliance being inspected. Follow the lighting instructions and adjust thermostat so 
appliance will operate continuously.
4.  Determine that the pilot or burner is operating properly and that the main burner ignition operates 
satisfactorily, by interrupting and re-establishing the electrical power of the appliance in any convenient 
manner. Test the pilot or burner safety device to determine if it is operating properly by extinguishing the 
pilot or disconnecting the  ame safety circuit and pressure switch sensing tube from the pressure switch.
Figure 11










