Install Instructions

WARNING: never expose eyes or skin to UVC light from any source. Looking directly at the UVC light may cause permanent eye damage or blindness.
Never operate the UV-Aire™ AirPurifying System out of the plenum. Avoid touching the glass portion of the lamp with your hands.
CAUTION: MAKE CERTAIN THAT POWER HAS BEEN DISCONNECTED TO THE HVAC SYSTEM, AND THE 24 VAC
TRANSFORMER POWER SOURCE, BEFORE PROCEEDING WITH THE INSTALLATION!
8. Follow steps 9-20 in the Magnet Mount Installation section to complete the installation (see Figures 7, 8, 9).
WARNING: BEFORE RESTORING POWER TO THE HVAC SYSTEM OR THE TRANSFORMER POWER SOURCE,
VERIFY THAT NO OPENINGS EXIST THROUGH WHICH UVC RAYS FROM THE LAMP MAY ESCAPE. VERIFY THAT
ALL ACCESS PANELS AND DUCTWORK ETC. HAVE BEEN REPLACED AND SEALED IF NECESSARY, AND THAT
THE SAFETY VIEW PORT IS SECURELY FASTENED IN PLACE.
Figure 9
Figure 8
Figure 7
MAINTENANCE
1. Inspect and clean lamp at least every 6 months.
2. Replace your UV-Aire™ Air Purifying System lamp once a year to maintain the lamps maximum output
intensity. The lamp should operate continuously for maximum lamp life and light e ectiveness.
LAMP REPLACEMENT PROCEDURE
WARNING: DISCONNECT 120V POWER TO THE 24VAC TRANSFORMER BEFORE PROCEEDING WITH LAMP
REPLACEMENT OR OTHER MAINTENANCE. IF THE LAMP IS MOUNTED EXTERNALLY ON A PLENUM OR AIR
DUCT, DISCONNECT THE LAMP CABLE FROM THE LAMP BEFORE REMOVING THE LAMP FROM THE EXTERNAL
MOUNT BRACKET. VERIFY THAT THE LAMP IS NOT LIT BY LOOKING THROUGH THE SAFETY VIEWPORT BEFORE
REMOVING ANY ACCESS PANELS, OR THE LAMP FROM THE EXTERNAL MOUNT BRACKET.
1. Verify that the lamp is not lit by looking through the safety viewport.
2. Disconnect the Lamp Cable connector from end of lamp.
3. Remove the nuts holding the lamp on the mounting bracket and remove the lamp, using care to avoid
breaking the lamp.
NOTE: When replacing the lamp, always wipe o lamp before installing.
4. Install the replacement lamp onto the mounting bracket and tighten the nuts. Tip: leave the protective
packaging sleeve on the lamp (magnet mount only) on the lamp until the replacement procedure is complete,
to help protect the lamp from breakage.
NOTE: UV lamps contain a small amount of mercury, like a typical  uorescent lamp. Check with your local
waste management authority for local disposal or recycling requirements. According to the EPAs Universal
Waste Rule, these types of lamps may be disposed of into household waste.
5. Attach the Lamp Cable connector onto the end of the lamp.
6. After replacing lamp, make sure a new UV Hazard Warning Label (supplied with lamp replacement) is
applied to the HVAC equipment or ducting and dated with the date of installation.
7. Restore power to the HVAC system and the transformer power source. Look through the Safety Viewport
to verify that the lamp is lit.