CONNECTING VENTER TO APPLIANCE
TheventingsystemshouldbeinstalledandsupportedinaccordancewiththeNationalFuelGasCodeANSI
Z233.1,orinaccordancewithanylocalcodes.Aventpipeconnectorshallbesupportedforthedesignand
weight of the material employed, to maintain clearances, prevent physical damage and separation of joints. A
vent pipe increaser or reducer may be required for connecting the venter to the vent system. Smaller vent pipe
sizes than a chimney-vented system may be used for the vent system.
Route the vent pipe from the appliance to the venter using as few elbows as possible. The horizontal section
of the vent pipe should have a slight upward slope from the appliance to the venter. For clearances to
combustiblematerials,multipleapplianceventingandotherinstallationrequirements,refertotheNational
FuelGasCodeANSIZ223.1,and/oranyapplicablelocalcodesorappliancemanufacturer'sinstallation
instructions.
GENERAL WIRING INSTRUCTIONS
CAUTION: Disconnect electrical power before wiring power venter!
ThePVOisdesignedtobeusedwithapplianceswith120VACcontrolsystems.Wiretheventermotorand
controlsinaccordancewiththeNationalElectricalCode,and/orapplicablelocalcodes.UNITMUSTBE
GROUNDED.Checkgroundcircuittomakecertainthattheunithasbeenproperlygrounded.Thewiring
shouldbeprotectedbyanover-currentcircuitdeviceratedat15amperes.CAUTIONMUSTbetakento
ensure that the wiring does not come in contact with any heat source. All line voltage and safety control
circuitsbetweentheventerandapplianceMUSTbewiredinaccordancewiththeNationalElectricalCode
for Class 1 wiring, or equivalent methods. Refer to wiring diagrams B & C for typical wiring. For other wiring
diagrams, please contact Field Controls Technical Support.
NOTE:WhenapplyingpowertothePVOforthersttime,theventermotormayormaynotrunforupto10
minutes. This is normal, and will not affect the operation of the system.
INSTALLATION OF POWER VENTER
CAUTION:Failuretoinstall,maintainand/oroperatethepowerventingsysteminaccordancewith
manufacturer'sinstructionswillresultinconditionswhichmayproducebodilyinjuryand/orpropertydamage.
Remove power venter from box and inspect unit for damage. If the carton has been crushed or mutilated, 1.
check unit very carefully for damage. Rotate venter wheel to ensure that the motor and venter wheel rotate
freely.DONOTinstallifanydamageisapparent.Refertounitsizingcharttocheckproperventersizing.
LocationoftheterminationoftheventingsystemshouldbeinstalledinaccordancewiththeNationalFuel2.
GasCode,ANSIZ233.1,manufacturer'srecommendations,and/orlocalcodeswhichareapplicable.See
the following requirements or refer to Diagram A for typical locations.
The exit termination of mechanical draft systems shall not be less than 7' above grade when located a.
adjacent to public walkways.
A venting system shall terminate at least 3' above any forced air inlet located within 10'.b.
Theventingsystemofotherthanadirectventapplianceshallterminateatleast4'below,4'horizontallyc.
from,or1'aboveanydoor,window,orgravityairinletintothebuilding.Whenventingoilred
equipment with a Field Controls CAS-2 series Airboot
®
kit, the intake air hood can be mounted within
12"ofthepowerventerexhaust.
Theventterminationofadirectventappliancewithaninputof50,000BTU/Hrorless,shallbelocatedd.
atleast9"fromanyopeningthroughwhichventedgasescouldenterthebuilding.Withaninputover
50,000BTU/Hr,a12"terminationclearanceshallberequired.
The vent termination point shall not be installed closer than 3' from an inside corner of an e.
L-shaped structure.
The vent termination should not be mounted directly above or within 3' horizontally from an oil tank vent f.
or gas meter.
Thebottomoftheventterminalshallbelocatedatleast12"abovenishedgrade.g.