Instructions / Assembly

page8
Figure 6
Figure 7
Figure 8
PRESSURE SWITCH ADJUSTMENT
Withtheventerairowsetandthe1.
appliance operating at the best operating
efficiency, adjust the pressure switch by
rotating the adjustment screw clockwise until
the burner shuts off.
Rotate the adjustment screw 2.
counterclockwise until the burner fires.
Rotate the adjustment screw an additional 3.
1
4 turn counterclockwise to ensure proper
switchsetting.(SeeFigure6)
POST PURGE TIMER ADJUSTMENT
Toadjustthepostpurgetime,refertoFigures7&8.
For timer that looks like Figure 7: Rotate the timer
adjustment on the timer clockwise to increase the
operation time. To decrease the operation time, rotate
the timer adjustment counterclockwise.
FortimerthatlookslikeFigure8:Rotatethetimer
adjustment on the timer counterclockwise to increase
the operation time. To decrease the operation time,
rotate the timer adjustment clockwise.
*Typical post purge time should be between
3to5minutes.