Specification

Technical Service: 800.742.8368 • fieldcontrols.com 13
Venting
See Calculating Equivalent Feet of a Vent System
* PVG PAKs include a Power Venter, a 4" MG-1 Draft Control, and a 4" Vent Hood
** PVE-1200 requires a CK-Kit
W
H
See Calculating Equivalent Feet of a Vent System
* PVE-1200 requires a CK-Kit
Select venter according to the actual rated maximum GPH Input. GPH ratings at 100 PSI
Do not exceed maximum oil GPH Input
PVG - Gas and PVG PAK
Maximum Equivalent Horizontal Pipe Length (Feet)
Model DIA.
(BTU/hr Input)
25,000 55,000 70,000 100,000 145,000 220,000 310,000 400,000 520,000 610,000 900,000 1,250,000
PVG-100
PVGPAK-100*
3" 270 100
4" 455 169 144 100
PVG-300
PVGPAK-300*
4" 305 145 64
5" 247 100 54
6" 334 147 74
PVG-600
5" 413 181 91 54
6" 146 87 52
8" 216 134 86 66
PVE-1200**
8" 313 180
10" 390 290 80
Specifications
UNIT DIMENSIONS (INCHES) ELECTRICAL DATA
Model Height Width Depth Inlet/Outlet Volts Hz RPM Watts Amps Therm. Prot.
PVG/PVO-100
7.50 7.75 7.00 4.00 115 60 3000 145 2.1 YES
PVG/PVO
7.50 9.25 7.00 4.00 115 60 3000 145 2.1 YES
PVG/PVO-600
8.75 9.75 8.50 5.00 115 60 3000 167 1.5 YES
PVE-1200
13.75 11.50 13.50 8.00 115 60 1750 186 3.9 YES
PVO - Oil
Maximum Equivalent Horizontal Pipe Length (Feet)
Model DIA.
GPH Input
0.40 0.50 0.75 1.00 1.50 2.25 3.00 3.75 4.00 6.00 9.00
PVO-300
4" 287 150 75
5" 257 120 51
6" 346 172 70
PVO-600
5" 428 212 86 46
6" 143 74 51
8" 211 116 84 77
PVE-1200*
8" 436 385 208
10" 407 311 74
Indoor Mounted Power Venters for Oil & Gas
PV Power Venters