Specification
Technical Service: 800.742.8368 • fieldcontrols.com 13
Venting
† See Calculating Equivalent Feet of a Vent System
* PVG PAKs include a Power Venter, a 4" MG-1 Draft Control, and a 4" Vent Hood
** PVE-1200 requires a CK-Kit
W
D
H
† See Calculating Equivalent Feet of a Vent System
* PVE-1200 requires a CK-Kit
Select venter according to the actual rated maximum GPH Input. GPH ratings at 100 PSI
Do not exceed maximum oil GPH Input
PVG - Gas and PVG PAK
Maximum Equivalent Horizontal Pipe Length (Feet)
†
Model DIA.
(BTU/hr Input)
25,000 55,000 70,000 100,000 145,000 220,000 310,000 400,000 520,000 610,000 900,000 1,250,000
PVG-100
PVGPAK-100*
3" 270 100 – – – – – – – – – –
4" 455 169 144 100 – – – – – – – –
PVG-300
PVGPAK-300*
4" – – – 305 145 64 – – – – – –
5" – – – – 247 100 54 – – – – –
6" – – – – 334 147 74 – – – – –
PVG-600
5" – – – – 413 181 91 54 – – – –
6" – – – – – – 146 87 52 – – –
8" – – – – – – 216 134 86 66 – –
PVE-1200**
8" – – – – – – – – – 313 180 –
10" – – – – – – – – – 390 290 80
Specifications
UNIT DIMENSIONS (INCHES) ELECTRICAL DATA
Model Height Width Depth Inlet/Outlet Volts Hz RPM Watts Amps Therm. Prot.
PVG/PVO-100
7.50 7.75 7.00 4.00 115 60 3000 145 2.1 YES
PVG/PVO
7.50 9.25 7.00 4.00 115 60 3000 145 2.1 YES
PVG/PVO-600
8.75 9.75 8.50 5.00 115 60 3000 167 1.5 YES
PVE-1200
13.75 11.50 13.50 8.00 115 60 1750 186 3.9 YES
PVO - Oil
Maximum Equivalent Horizontal Pipe Length (Feet)
†
Model DIA.
GPH Input
0.40 0.50 0.75 1.00 1.50 2.25 3.00 3.75 4.00 6.00 9.00
PVO-300
4" – – 287 150 75 – – – – – –
5" – – – 257 120 51 – – – – –
6" – – – 346 172 70 – – – – –
PVO-600
5" – – – 428 212 86 46 – – – –
6" – – – – – 143 74 51 – – –
8" – – – – – 211 116 84 77 – –
PVE-1200*
8" – – – – – – – 436 385 208 –
10" – – – – – – – – 407 311 74
Indoor Mounted Power Venters for Oil & Gas
PV Power Venters