Specification
Wiring
Wiring Diagrams
74 Customer Service: 252.522.3031
CAS-6, CAS-7 Controlled by P-Sensor, 120 Volt Application
CAS-6, CAS-7 Controlled by P-Sensor, 24 Volt Application
120VAC / 24VAC
*
CAS-6 / CAS-7
GND
GND
WHT
BLK
R
C
White
Black
Green
24VAC Control Relay Installed (FC P/N 46080200)
COM N.O.
P-SENSOR
(FC P/N 46679400)
CAS-6, CAS-7 CONTROLLED BY P-SENSOR, 24VAC
*24VAC transformer will have a minimum of 20VA, not
to exceed 40VA. Class 2 type may be used.
IMPORTANT: If using the quick connect crimp
terminals supplied with the P-Sensor, use stranded wire
only. Do not crimp terminals with the solid copper wire.
WIRING INSTRUCTIONS: MUST be installed by a Certified Electrician. Wire the CAS unit in accordance with the National Electric Code
and applicable local codes. UNIT MUST BE GROUNDED. Check the ground circuit to make certain that the unit has been properly
grounded. The wiring should be protected by an over-current circuit device rated at 15 amperes. CAUTION must be taken to ensure that
the wiring does not come in contact with any heat source. All line voltage and control circuits between the CAS unit and the appliance
MUST be wired in accordance with the National Electrical Code for Class I wiring or equivalent.
(FC P/N 46679400)
White
Black
Green
GND
GND
T3T2T1
COM N.O.
P-SENSOR
CAS-6, CAS-7 CONTROLLED BY P-SENSOR, 120VAC
GND
GND
120VAC Control Relay Installed (FC P/N 46111100)
CAS-6 / CAS-7
* IMPORTANT: P-Sensor MUST be mounted in a metal
junction box/enclosure supplied by the installer in
order to be compliant with National Electrical Code for
Class 1 wiring. If using supplied quick connect
terminals, wire must be stranded. Do not crimp
terminals with the solid copper wire.
WIRING INSTRUCTIONS: MUST be installed by a Certified Electrician. Wire the CAS unit in accordance with the National Electric Code
and applicable local codes. UNIT MUST BE GROUNDED. Check the ground circuit to make certain that the unit has been properly
grounded. The wiring should be protected by an over-current circuit device rated at 15 amperes. CAUTION must be taken to ensure that
the wiring does not come in contact with any heat source. All line voltage and control circuits between the CAS unit and the appliance
MUST be wired in accordance with the National Electrical Code for Class I wiring or equivalent.
metal enclosure
WIRING INSTRUCTIONS: MUST be installed by a Certified Electrician. Wire the CAS unit in accordance with the National Electric Code
and applicable local codes. UNIT MUST BE GROUNDED. Check the ground circuit to make certain that the unit has been properly
grounded. The wiring should be protected by an over-current circuit device rated at 15 amperes. CAUTION must be taken to ensure that
the wiring does not come in contact with any heat source. All line voltage and control circuits between the CAS unit and the appliance
MUST be wired in accordance with the National Electrical Code for Class I wiring or equivalent.
For CAS with Sensors