SWG SIDEWALL POWER VENTING KIT Installation Specifications For The Following Furnaces Certified As A Component Part of The Furnace Application. This instruction sheet contains OEM specific information that supercedes the provided instruction manual where applicable. All field wiring shown in included wiring diagrams are correct regardless whether the CK-43 or CK-43F is used.
SWG-4AM AMANA SIDEWALL POWER VENTING KIT Field Controls P/N 46205411 Kit Includes: SWGII-4HD Sidewall Power Venter CK-43 Control Kit Includes: 4" MG-1 Barometric Draft Control Fan Proving Switch Adjustable Post Purge Recommended For Use On The Following Amana Model Furnaces: GBI GCIA GCIC GMI GUI GUIB GUID GCIB GCI GSI GHI GUIC GUIA NOT For Use On The Following Amana Model Furnaces: GCIS GUIS GUIV Furnace Configuration and Vent Pipe Restrictions Type B-1 vent pipe shall be used to join the furnace
For Furnace Models GBI, GCI, GHI, GSI, and GUI Maximum Maximum Installer BTU/Hr. Diameter of Equivalent Length Equivalent Length Provided Flue Flue Collar on Furnace Pipe Transition (ft.) for 4" Vent Pipe (ft.) for 5" Vent Pipe Size Diameters 45,000 3" 3" to 4" 100 100 70,000 3" 3" to 4" 100 100 90,000 3" 3" to 4" 100 100 115,000 4" None 85 95 140,000 4" None 65 80 For Furnace Models GMI Installer BTU/Hr.
SWG-4AT AMERICAN STANDARD AND TRANE SIDEWALL POWER VENTING KIT Field Controls P/N 46205405 Kit Includes: SWGII-4HD Sidewall Power Venter CK-43F Control Kit Includes: 4" MG-1 Barometric Draft Control Fan Proving Switch Fixed post purge For Use With The Following American Standard And Trane Furnaces: AUD-C TUD-C AUD-R TUD-R CUE-A TUE-A ADD-C TDD-C ADD-R TDD-R CDE-A TDE-A Furnace Configuration And Vent Pipe Restrictions: Furnace Input BTU/Hr 40,000 60,000 80,000 100,000 120,000 140,000 Diameter Of Vent Pip
Page 5
SWG-4A ARMSTRONG SIDEWALL POWER VENTING KIT Field Controls P/N 46205407 Kit Includes: SWGII-4HD Sidewall Power Venter CK-43F Control Kit Includes: 4" MG-1 Barometric Draft Control Fan Proving Switch Fixed post purge For use with Armstrong furnace models that begin with the following: AMEG6G EG5G EG6G EG7G EG8G GCJ GHJ GUJ Furnace Configuration and Vent Pipe Restrictions Model Number Configuration AMEG6G EG5G EG6G EG7G EG8G GCJ GHJ GUJ Upflow Lowboy Upflow Downflow Horizontal Downflow-Horizontal U
SWG-4B BARD SIDEWALL POWER VENTING KIT Field Controls P/N 46205410 Kit Includes: SWGII-4HD Sidewall Power Venter CK-43F Control Kit Includes: 4" MG-1 Barometric Draft Control Fan Proving Switch Fixed post purge For Use With The Following Bard Standard Furnaces: Upflow IH60D36 (A,B) IH85D48 (A,B,D) IH115D48 (A,B) IH115D60A IH145D60A Downflow IC60D36A IC85D42 (A,D) IC115D48A ----------- Lowboy -----IL85D42 (A,D) IL115D48A -----IL145D60A Unit Selection Table: Furnace Input Btu/Hr Diameter Of Vent Installer
SWGII-4CC CARRIER SIDEWALL POWER VENTING KIT Field Controls P/N 46205403, Carrier P/N KGASW03012SP Kit Includes: SWGII-4HD Sidewall Power Venter CK-43CC Control Kit Includes: 4" MG-1 Barometric Draft Control Fan Proving Switch Fixed post purge For Use With The Following Carrier Furnace Models: 58UXT 58WAV 58DXT 58ZAV 58UXV 58PAV 58UHV 58RAV 58TUA GB1AAV 58TMA GB3AAV For Use With The Following BDP Furnace Models: 330JAV 376CAV 331JAV 383KAV 333JAV 373LAV 333BAV 480BAV 330AAV 481BAV 331AAV GB1AAV
* † § ‡ The furnace's Draft Safeguard switch assembly can remain in place as installed at the factory, or the Draft Safeguard switch assembly can be removed (relief box opening sealed with Block-off Plate and switch replaced with Splice Connector from Kit KGASW0101/02012SP). The Draft Safeguard switch assembly must remain installed and operational in the furnace. See Equivalent Length Table II. Fewer elbows permit longer straight length & vice-versa.
SWG-4CD CONSOLIDATED SIDEWALL POWER VENTING KIT Field Controls P/N 46205408 Kit Includes: SWGII-4HD Sidewall Power Venter WMO-1 Thermal Safety Switch (Must be purchased separately if using other venting kit on Consolidated Furnaces.
1. 2. Maximum equivalent vent length is 63 feet for all furnaces listed! The SWG-4CD power venter kit must be installed using type B-1 vent pipe only! General Wiring For complete installation information refer to the Field Controls SWG-4CD Power Venter Installation Manual for details (P/N 46333600.
3” x 90° elbow - reduce vent length by 3 feet for each elbow Standard 3" single walled galvanized venting or 3" Type B vent pipe should be used. Draft Control Installation: 1. Install a 3" vent pipe tee of the same material as the vent piping 12" to 24" away from the outlet of the boiler's blower. Then place a 3"X4" reducer in the tee for mounting the barometric draft control as shown in the Figure below. 2.
General Wiring For complete installation information refer to the Field Controls SWG-4D,5D Power Venter Installation Manual for details (P/N 46298400.
General Wiring: For complete installation information refer to the Standard Field Controls SWG/SWGII series Power Venter Installation Manual (P/N 46139100), and the CK-43F Control Kit Installation Manual (P/N 46285100) for details.
Unit Sizing: BTU/HR Input Diameter Of Vent Pipe To Flue Pipe Transition Size Power Venter Diameter 50,000 3” 3” TO 4” 75,000 4” None Required 100,000 4” None Required 125,000 4” None Required Maximum Pipe Length - (3) 90° Elbows, 30 feet of vent pipe and reducer or increaser if required. Minimum Pipe Length - (1) 90° Elbow, 5 feet of vent pipe and a reducer or increaser if required.
SWG-4ICF INTER-CITY SIDEWALL POWER VENTING KIT Field Controls P/N 46205413 Kit Includes: SWGII-4HD Sidewall Power Venter CK-43F Control Kit Includes: 4" MG-1 Barometric Draft Control Fan Proving Switch Fixed post purge For Use With The Following Series Of Furnaces GDJ NCC5 GDL NDC7 GNI NDN5 GNJ NTC5 GNL NTC7 CUGE NTN5 CUG5 NUG5 Unit Selection Table BTU/HR Input 50,000 75,000 100,000 125,000 Diameter Of Vent Pipe To Power Venter 3" 4" 4" 4" Flue Pipe Transition Size Diameter 3" TO 4" None Required N
SWG-4L LENNOX SIDEWALL POWER VENTING KIT Field Controls P/N 46205402 Kit Includes: SWGII-4HD Sidewall Power Venter CK-43 Control Kit Includes: 4" MG-1 Barometric Draft Control Fan Proving Switch Adjustable post purge For Use On The Following Lennox Series Furnaces: G23 G24M 80MGF Unit Selection And Maximum Vent Length Table BTU/Hr Input Diameter Of Vent Pipe Collar On Furnace 45,000* 3" 50,000 3" 60,000* 3" 75,000* 4" 100,000* 4" 120,000* 4" 125,000 5" 140,000* 4" 150,000 5" *G24M/80MGF Input Rates Ins
SWG-4R RHEEM SIDEWALL POWER VENTING KIT Field Controls P/N 46205409 Kit Includes: SWGII-4HD Sidewall Power Venter CK-43R Control Kit Includes: 4" MG-1 Barometric Draft Control Fan Proving Switch Fixed post purge For Use With The Following Rheem, Ruud, And Weatherking Model Series Furnaces: (-)GDG* (-)GDJ* (-)GPJ* (-)GVJ* (-)GVA (-)GYA (-)GVH* (-)GDC (-)GVB (-)GPH* (-)GLG (-)GLC (-)GDE (-)GYB WGVAH (-)GLH* (-)GVG (-)GLJ* (-)GLE (-)GVC (-)GYC WGVAG WGDAG WGLAG *Indicated models are CGA certified with the
Vent Specifications: 1. 2. 3. 4. 5. 6. All vent pipe and elbows must be Type B, double wall vent. The maximum vent length is 30 feet with a maximum of three 90° elbows. The minimum vent length is 5 feet. Use 3" vents for models with inputs through 75,000 BTU/Hr. Use 4" vents for models with inputs over 75,000 BTU/Hr. A 4" barometric damper is included in the power venter kit.
P1UK PAKU P2MP PBKM P9MP XEM P2DP PBKD P3UC XED P9UC PCMU P3CC PKMU P9CC PCMD PKMD Unit Sizing And Equivalent Footage Refer to the following to choose the proper size vent pipe and fittings for connecting the SWG power venter to the appliance. The following table also lists the maximum equivalent length of vent pipe allowed, depending on the appliance input rating and the diameter of vent pipe used.