SWG-4AM AMANA SIDEWALL POWER VENTING KIT
Field Controls P/N 46205411
Kit Includes:
SWGII-4HD Sidewall Power Venter
CK-43 Control Kit
Includes: 4" MG-1 Barometric Draft Control
Fan Proving Switch
Adjustable Post Purge
Recommended For Use On The Following Amana Model Furnaces:
GBI GCIC GUI GUID GCI GHI GUIA
GCIA GMI GUIB GCIB GSI GUIC
NOT For Use On The Following Amana Model Furnaces:
GCIS GUIS GUIV
Furnace Configuration and Vent Pipe Restrictions
Type B-1 vent pipe shall be used to join the furnace to the venting system and for the entire length of
the venting system. Exception: Up to 24" of single wall vent pipe may be used to connect the furnace
to the barometric damper. The barometric damper tee may be single wall. Type B-1/double wall vent
pipe MUST be used from the barometric damper tee to the power venter.
For Furnace Models GUIA, GUIB, GUIC, and GUID
BTU/Hr. Diameter of
Flue Collar
on Furnace
Installer
Provided Flue
Pipe Transition
Size Diameters
Maximum
Equivalent Length
(ft.) for 4" Vent Pipe
Maximum
Equivalent Length
(ft.) for 5" Vent Pipe
46,000 4" None 100 100
69,000 4" None 100 100
92,000 4" None 100 100
115,000 4" None 85 95
138,000 4" None 65 80
For Furnace Models GCIA, GCIB, and GCIC
BTU/Hr. Diameter of
Flue Collar
on Furnace
Installer
Provided Flue
Pipe Transition
Size Diameters
Maximum
Equivalent Length
(ft.) for 4" Vent Pipe
Maximum
Equivalent Length
(ft.) for 5" Vent Pipe
46,000 3" 3" to 4" 100 100
69,000 3" 3" to 4" 100 100
92,000 3" 3" to 4" 100 100
115,000 3" 3" to 4" 85 95
138,000 3" 3" to 4" 65 80