User Guide
1918
Resistance (Ω)
Used for “ohming out” a compressor. A 0.01Ω resolution is useful to
test the resistance between the terminal poles because the values are
typically very low. Resistance is default test in this switch position. For
best practice, use a megger (Fieldpiece SMG5) to measure motor winding
insultion to ground.
Ranges: 100Ω, 1000Ω, 10kΩ, 100kΩ, 1000kΩ, 10MΩ, 50MΩ
Resolution: 0.01Ω
Accuracy: ±(1.0% + 15) 100Ω, ±(1.0% + 5) 1000Ω to 100kΩ, ±(1.5%
+ 5) 1000kΩ, ±(3.0% + 5) 10MΩ to 50MΩ
Open circuit volts: -1.1VDC typical, -3.2VDC (100Ω range)
Overload Protection: 600VDC or 600VAC rms
Continuity (
OO
FF
FF
M
FD
NCV
VAC
V
DC
AAC
Hz
Hz
%
°C
°F
SC56
AUTO OFFTRUE RMS
CAT III
600V
TEMP
K-TYPE
30V
MAX
SEL
HOLD
INRUSH
)
Perfect for checking isolated fuses, use the continuity function to test
whether a circuit is open (no beep, no green LED) or closed (beep and
green LED). Press SELECT once to enter Continuity mode.
Range: 100Ω Resolution: 0.01Ω Response time: 100ms
Audible beep: <30Ω
Visual Indicator: Green LED
Overload Protection: 600VDC or 600VAC rms
Diode Test (
OO
FF
FF
M
FD
NCV
V
AC
VDC
AAC
Hz
Hz
%
°C
°F
SC56
AUTO OFFTRUE RMS
CAT III
600V
TEMP
K-TYPE
30V
MAX
SEL
HOLD
INRUSH
)
Test diodes for proper forward and reversed-biased functions. A
voltage will display in forward-bias and “OL” in reversed-bias. Press SELECT
twice to enter Diode mode.
Test current: 0.8mA (Approx.) Accuracy: ±(1.5% + 5)
Open circuit volts: 3.2VDC typical Audible beep: <0.05V
Visual Indicator: Green LED
Overload Protection: 600VDC or 600VAC rms