- Driver Manual (Supplement to the FieldServer Instruction Manual) FS-8700-16 Bacnet PTP - Serial APPLICABILITY & EFFECTIVITY Effective for all systems manufactured after September 2008 Driver Version: Document Revision: 1.
FS-8700-16 BACnet PTP Serial Driver Manual Table of Contents TABLE OF CONTENTS 1. BACNET DESCRIPTION................................................................................................................... 3 2. DRIVER SCOPE OF SUPPLY........................................................................................................... 3 2.1. 2.2. 3. 4. Supplied by FieldServer Technologies for this Driver .................................................
FS-8700-16 BACnet PTP Serial Driver Manual 1. Page 3 of 20 BACnet Description The BACnet PTP driver allows the FieldServer to transfer data to and from devices using the BACnet protocol over a serial RS-232 physical layer. The FieldServer can emulate either a Server or Client. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer. 2. Driver Scope of Supply 2.1.
FS-8700-16 BACnet PTP Serial Driver Manual 3. Page 4 of 20 Hardware Connections 3 It is possible to connect a BACnet device to any of the eight RS-232 ports. These ports just need to be configured for BACnet in the configuration file.
FS-8700-16 BACnet PTP Serial Driver Manual 4. Page 5 of 20 Configuring the FieldServer as a BACnet Client For a detailed discussion on FieldServer configuration, please refer to the FieldServer Instruction Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” sample files provided with the FieldServer).
FS-8700-16 BACnet PTP Serial Driver Manual Page 6 of 20 Example // FieldServer FieldServer Title, BACnet_PTP, 4.3.
FS-8700-16 BACnet PTP Serial Driver Manual 4.5. Client Side Map Descriptors 4.5.1. FieldServer Related Map Descriptor Parameters Column Title Map_Descriptor_Name Data_Array_Name Data_Array_Offset Function 4.5.2.
Data_Array_Name, DA_DI_01, DA_DI_01, DA_DI_01, DA_DO_01, DA_DO_01, DA_DO_01, Map_Descriptors Map_Descriptor_Name, CMD_DI_01, CMD_DI_02, CMD_DI_03, CMD_DO_01, CMD_DO_02, CMD_DO_03, Data_Array_Offset, 0, 1, 2, 0, 1, 2, Data_Array_Offset, 0, 1, 2, 0, 1, 2, Function, RDBC, RDBC, RDBC, RDBC, RDBC, RDBC, Function, RDBC, RDBC, RDBC, RDBC, RDBC, RDBC, Node_Name, BCU_1, BCU_1, BCU_1, BCU_1, BCU_1, BCU_1, Node_Name, BCU_1, BCU_1, BCU_1, BCU_1, BCU_1, BCU_1, Data_Type, DI, DI, DI, DO, DO, DO, Data_Type, AI, AI, A
FS-8700-16 BACnet PTP Serial Driver Manual 5. Page 9 of 20 Configuring the FieldServer as a BACnet Server For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” sample files provided with the FieldServer).
FS-8700-16 BACnet PTP Serial Driver Manual 5.2. Page 10 of 20 Server Side Connection Descriptions Section Title Connections Column Title Port Port name Baud* Specify baud rate Parity* Data_Bits* Stop_Bits* Protocol Specify parity Specify data bits Specify stop bits Specify Protocol Used Function Legal Values 7 P1-P8 110; 300; 600; 1200; 2400; 4800; 9600; 19200; 38400; 57600; 115000 Odd, Even, None 7, 8 1,2 BACnet_PTP Example // Server Side Connections Connections Port, P1, 5.3.
FS-8700-16 BACnet PTP Serial Driver Manual 5.4. Server Side Map Descriptors 5.4.1. FieldServer Specific Map Descriptor Parameters Column Title Function Legal Values Up to 32 alphanumeric characters.
Map_Descriptors Map_Descriptor_Name, SMD_DI_01, SMD_DI_02, SMD_DI_03, SMD_DO_01, SMD_DO_02, SMD_DO_03, Virtual_BCU_11, Virtual_BCU_11, Virtual_BCU_11, Virtual_BCU_11, Virtual_BCU_11, Virtual_BCU_11, Server, Server, Server, Server, Server, Server, AI, AI, AI, AO, AO, AO, Data_Type Deg_F, Deg_F, Deg_F, %RH, %RH, %RH, Units, Data_Type, DI, DI, DI, DO, DO, DO, Present_Value, Present_Value, Present_Value, Present_Value, Present_Value, Present_Value, Property, Node_Name, Virtual_BCU_11, Virtual_BCU_11, V
FS-8700-16 BACnet PTP Serial Driver Manual Page 13 of 20 Appendix A. Driver Notes Appendix A.1. AI AO AV BI BV MI MO MV Data_Type Legal Values – Abbreviation Descriptions ANALOG_INPUT ANALOG_OUTPUT ANALOG_VALUE BINARY_INPUT BINARY_VALUE MULTI_STATE_INPUT MULTI_STATE_OUTPUT MULTI_STATE_VALUE FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll Free: 888-509-1970 email: support@fieldserver.
FS-8700-16 BACnet PTP Serial Driver Manual Page 14 of 20 Appendix B. Advanced Topics Appendix B.1. BACnet Object Names When an external BACnet Client builds a list of Object Names, the BACnet Server Map Descriptor name determines the BACnet Object Name. If the Map Descriptor length is greater than 1, then the Object Name will be suffixed with the index into the Map Descriptor.
FS-8700-16 BACnet PTP Serial Driver Manual Appendix B.4. Page 15 of 20 Network number The default Network number of a FieldServer is 5. In order to ensure communication between the BACnet Client and all Servers on a BACnet network, however, it may be necessary to assign a unique network number to each FieldServer. A unique network number will need to be assigned if both of the following conditions are true: • The FieldServer has multiple BACnet Server nodes.
Data_Array_Name, DA_MI_01, Object_ID, 1 Function, Server Data_Array_Length 100 Data_Array_Name, DA_MI_01, Data_Array_Index, 1, Data_Array_Index, 0, Node_Name, N1 11, Length, 1, Length, 1, Preload_Data_Index 0 Node_Name, N1 11, Preload_Data_Format, STRING, FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll Free: 888-509-1970 email: support@fieldserver.
FS-8700-16 BACnet PTP Serial Driver Manual Page 17 of 20 Appendix C. Troubleshooting Tips Appendix C.1. • • • • • • • • • • Debugging a BACnet connection – Hints and Tips Disconnect the FieldServer from the BACnet network when transferring images to the BCU. If duplicate object instances are accidentally configured in the FieldServer, the second call of the instance will overwrite the first one. This may cause a BACnet Object to be “lost.
FS-8700-16 BACnet PTP Serial Driver Manual Page 18 of 20 Appendix D.
FS-8700-16 BACnet PTP Serial Driver Manual Unit imperial-gallons imperial-gallons-per-min inches inches-of-mercury inches-of-water Joules joules-per-degree-kelvin joules-per-kilogram-degree-kelvin joules-per-kilogram-dry-air Kilograms kilograms-per-hour kilograms-per-minute kilograms-per-second Kilohertz kilohms Kilojoules kilojoules-per-kilogram kilometers-per-hour Kilopascals kilovolt-amperes kilovolt-amperes-reactive kilovolts kilowatt-hour-per-square-foot kilowatt-hour-per-square-meter kilowatt-hours k
FS-8700-16 BACnet PTP Serial Driver Manual Unit No-Units ohms parts-per-billion parts-per-million Pascals Percent percent-obscuration-per-foot percent-obscuration-per-meter percent-per-second percent-relative-humidity Per-hour per-minute per-second pounds-force-per-square-inch Pounds-mass pounds-mass-per-hour pounds-mass-per-minute pounds-mass-per-second Power-Factor psi-per-degrees-fahrenheit radians revolutions-per-minute seconds square-centimeters square-feet square-inches square-meters Therms ton-hours