Technologies Computer Driver Instruction Manual

FS-8700-16 BACnet PTP Serial Driver Manual Page 16 of 20
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll Free: 888-509-1970 email: support@fieldserver.com
Appendix B.5. BACnet State Text Preload
Method 1 – Using a Single Data Array:
Data_Arrays
Data_Array_Name,
Data_Format,
Data_Array_Length
DA_MI_01, UINT16, 100
DA_STATE_TXT, BYTE, 200
Preloads
Data_Array_Name,
Preload_Data_Value, Preload_Data_Format,
Preload_Data_Index
DA_STATE_TXT, MyState1 MyState2 MyState3 MyState4 MyState5 MyState6, STRING, 0
Map_Descriptors
Map_Descriptor_Name,
Data_Type,
Object_ID,
Function,
Data_Array_Name,
Data_Array_Index,
Node_Name,
Length,
State_Text_Array
CMD_MI_01, MI, 1 Server DA_MI_01, 0, N1 11, 1, DA_STATE_TXT
Method 2 – Using an Offset/User Table:
//set up a look up table
Offset_Table,
Offset_Table_Name, Table_String, Table_Index_Value
FIRE_ALRM_TEXT, SYSTEM READY,
0
FIRE_ALRM_TEXT, ALARM,
1
FIRE_ALRM_TEXT, MAINTENANCE,
2
FIRE_ALRM_TEXT, OFF-LINE,
3
FIRE_ALRM_TEXT, IN SERVICE,
4
FIRE_ALRM_TEXT, OTHER,
5
Data_Arrays
Data_Array_Name,
Data_Format,
Data_Array_Length
DA_MI_01, UINT16, 100
Map_Descriptors
Map_Descriptor_Name,
Data_Type,
Object_ID,
Function,
Data_Array_Name,
Data_Array_Index,
Node_Name,
Length,
State_Text_Array
CMD_MI_01, MI, 1 Server DA_MI_01, 1, N1 11, 1, FIRE_ALRM_TEXT