A Sierra Monitor Company Driver Manual (Supplement to the FieldServer Instruction Manual) FS-8700-23 Cleaver Brooks Hawk APPLICABILITY & EFFECTIVITY Effective for all systems manufactured after May 1, 2001 Driver Version: 1.
FS-8700-23 Cleaver Brooks Hawk Driver Manual Table of Contents Table of Contents 1. CB-Link Description........................................................................................................3 2. 2.1. 2.2. Driver Scope of Supply...................................................................................................4 Provided by FieldServer Technologies for this driver ..................................................4 Provided by the Supplier of 3rd Party Equipment..........
FS-8700-23 Cleaver Brooks Hawk Driver Manual 1. Page 3 of 13 CB-Link Description The CB-Link driver allows the FieldServer to transfer data to and from devices over RS-485 using CB-Link protocol. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer. Refer to “Model 833-2771 CB-Link” Manual #65-0216 and “Model 833-2757 General Purpose Interface ControlBus Module” Manual #65-0220 from Cleaver Brooks.
FS-8700-23 Cleaver Brooks Hawk Driver Manual 2. Page 4 of 13 Driver Scope of Supply 2.1. Provided by FieldServer Technologies for this driver Fieldserver Technologies Part # SPA59137 2.2. Description RS-485 7-way connector adapter with attached cable Provided by the Supplier of 3rd Party Equipment PART # DESCRIPTION CB-Link Controller FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.
FS-8700-23 Cleaver Brooks Hawk Driver Manual 3. Page 5 of 13 Hardware Connections The FieldServer can be connected to the CB – Link device as shown below. Configure the PLC according to manufacturer’s instructions !" #$ % $ & % '( ' ( ( '( # ( $ )( % ( ) ) % ))* * # Net 1 Gnd _ DC AUX Power Net 2 + + ,-. + FG Gnd _ Power + 5 V 1 .
FS-8700-23 Cleaver Brooks Hawk Driver Manual 4. Page 6 of 13 Configuring the FieldServer as a ChB-Link Client For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” sample files provided with the FieldServer).
FS-8700-23 Cleaver Brooks Hawk Driver Manual 4.3. Page 7 of 13 Client Side Connection Descriptions Section Title Connections Column Title Function Legal Values Specify which port the device is connected to the Port R1-R2 FieldServer Baud Specify baud rate 9600 Parity Specify parity None IC_Timeout Inter-Character Timeout >10.0 s Squelch_Timer Squelch suppression time >0.
FS-8700-23 Cleaver Brooks Hawk Driver Manual 4.4. Page 8 of 13 Client Side Node Descriptors Section Title Nodes Column Title Node_Name Function Provide name for node CB Link_ID Device address Protocol Specify protocol used Legal Values Up to 32 alphanumeric characters See Section 4.4.1 A, B, and C below CB_Link Port Port connection R1-R2 Node_Type Specify controller connected to CBLink See Section 4.4.2 Example // Client Side Nodes Nodes Node_Name, CBH1, 4.4.1.
FS-8700-23 Cleaver Brooks Hawk Driver Manual 4.5. Page 9 of 13 Client Side Map Descriptors 4.5.1. FieldServer Related Map Descriptor Parameters Column Title Map_Descriptor_Name Data_Array_Name Data_Array_Offset Function 4.5.2. Function Name of this Map Descriptor. This Name refers to the variable in the related .bp2 property file.
FS-8700-23 Cleaver Brooks Hawk Driver Manual 4.5.4. // Page 10 of 13 Map Descriptor Example Client Side Map Descriptors Map_Descriptors Map_Descriptor_Name, Control_Source, Oper_Pressure, Data_Array_Name, DA_AI_01, DA_AI_01, Data_Array_Offset, 1, 2, Function, RDBC, RDBC, Node_Name, CBH1, CBH1, Scan_Interval, 10, 10, FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.
FS-8700-23 Cleaver Brooks Hawk Driver Manual Page 11 of 13 Appendix A. Advanced Properties Appendix A.1. Property Files Each Controller interfacing to the FieldServer requires associated property files (denoted by file extensions .bp1 and .bp2) to be loaded into the FieldServer. At present, the property files listed in the device information table below are preloaded onto the FieldServer when delivered. Other property files may be available upon request. Appendix A.2.
FS-8700-23 Cleaver Brooks Hawk Driver Manual Page 12 of 13 Appendix B. Device Information Table MAKE Honeywell Cleaver Brooks NETWORK INTERFACE UNIT MODEL NAME Q7700 Network Interface Unit 833-2771 CB-Link CONTROL MODULES MODEL No.
FS-8700-23 Cleaver Brooks Hawk Driver Manual Page 13 of 13 THIS PAGE INTENTIONALLY LEFT BLANK. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.