VSN700 Data Logger Data sheet

Monitoring and communication - VSN700 Data Logger
Technical data and types
Type code VSN700 Data Logger
Communication interfaces
Serial port interface
(2) RS-485 + (2) RS-232
Maximum devices per serial port
Physical limitation of 32 (reduced by poll rate, inverter data set size and logger type)
Fieldbus cable
RS-485 Shielded Twisted Pair. Recommend Belden # 1120A cable or # 3106A for 3 conductors
Ethernet port 0
Firewall protected Ethernet WAN port for Internet connection
Ethernet port 1
Local LAN with static IP address
Ethernet connections
RJ-45 Ethernet 10/100 base-T (LAN/WAN)
Communication protocols
Plant fieldbus protocols Aurora Protocol, Modbus RTU (SunSpec)
LAN/WAN protocols HTTP, DHCP, SSL, SSH, XML
Data logging specifications
Data sampling rate High frequency data sampling (less than 1 minute average)
Local storage Log data for 30 days based on 15-minute intervals (Days logged may be reduced by intervals shorter than 7 minutes)
Upgradeability Field upgradable over the Internet or locally via USB memory stick
Power supply
AC power supply input 100 - 240 VAC
DC power supply output 12 VDC, 1 A
Environmental parameters
Ambient temperature range
Logger only -40°F to 185°F (-40°C to 85°C); power supply 32°F -104°F (0°C-40°C)
Environmental protection
IP20
Relative humidity
< 85% Non-condensing
Mechanical parameters (per unit)
Dimensions (H x W x D)
133 mm x 132 mm x 31 mm (5,2” x 5.1” x 1,2”)
Weight
0.91 kg (2 lbs)
Mounting system
Screws through flanges
Warranty
Standard warranty
Two years
Accessories
VSN-MGR-DIN
Din rail mount kit to mount logger on a din rail
VSN800-12
Weather Station with sensors: ambient temperature, panel temperature, global irradiance
VSN800-14
Weather Station with sensors: ambient temperature, panel temperature, global irradiance, plane of array irradiance, wind speed
and direction
Compliance
Emissions
FCC Part 15 Class B, CISPR 22, EN 55022 conducted and radiated emission, EN55024
1) Please refer to the document “Accessories compatibility matrix” available at www.
fimer.com for information on the compatible models and/or devices.
Remark. Features not specifically listed in the present data sheet are not included in
the product
VSN700-05 specifications
Feature VSN700-05
Logging real-time power values 1, 3, 5, 15 minute configurable intervals
Modbus/TCP server Yes
Inverter control commands Yes
Devices supported
All FIMER inverters
1)
Up to 64 Modbus (RTU) supported devices
(from both FIMER and 3° party)