Data Sheet

4
I
Relays for automatic control of lighting
according to ambient light level - with
separate light sensor
11.42 - 1 CO + 1 NO 12A output contacts
Two independent outputs with individual lux
setting
Selector with 4 positions:
- Standard range (threshold setting 1…80x)
- High range (threshold setting 20…1000lx)
- continuous light (helpful during installation and
initial testing and for maintenance purposes)
- light off (useful for vacations)
For the first 6 working cycles (in total for
channels 1 & 2) the delay time (On and Off) is
reduced to zero in order to aid installation
LED status indication
11.91 - 1 CO 16A output contact
(+ auxiliary output for Power Module)
Daily time switch function - programmable to
inhibit main output (for energy saving)
Auxiliary output - directly driven by the
photosensor
Italian patent “Light feedback compensation”
principle
Sensitivity adjustment from 1 to 150lux
LCD status indication, set-up and programming
Internal battery for set-up/programming
without supply and for time/program back-up
in case of power failure (5 years)
Low stand-by power consumption
SELV separation between contact and supply circuit
Double insulation between supply and light sensor
35mm rail (EN60715) mount
Cadmium free contact material
Cadmium free light sensor (IC photo diode)
11.42 11.91
2 independent outputs
2 individual lux settings
4 position selector
Light dependent relay + time
switch
Auxiliary output (light
dependent) with 19.91 power
module available
For outline drawing see page 10
Contact specification
Contact configuration 1 CO (SPDT) + 1 NO (SPST-NO) 1 CO (SPDT) + 1 aux output*
* 11.91 auxiliary output:
12VDC, 1W max
Rated current/Maximum peak current A 12/24 (120 A - 5ms) 16/30 (120 A - 5ms)
Rated voltage/
Maximum switching voltage VAC 250/400 250/400
Rated load AC1 VA 3000 4000
Rated load AC15 (230VAC) VA 750 750
Nominal lamp rating:
2000 2000230V incandescent/halogen W
fluorescent tubes with
electronic ballast W 1000 1000
fluorescent tubes with
electromechanical ballast W 750 750
CFL W 400 400
230V LED W 400 400
LV halogen or LED with
electronic ballast W 400 400
LV halogen or LED with
electromechanical ballast W 800 800
Minimum switching load mW (V/mA) 1000 (10/10) 1000 (10/10)
Standard contact material AgSnO
2
AgSnO
2
Supply specification
Nominal voltage (U
N
) VAC (50/60Hz) 230 110…230
DC 110…230
Rated power VA (50Hz)/W 7.4/2.8 5/2.1
Operating range VAC (50Hz) (0.8…1.1)U
N
(0.8…1.1)U
N
DC (0.8…1.1)U
N
Technical data
Electrical life at rated load in AC1 cycles 100·10
3
100·10
3
Threshold setting: Standard range lx 1…80 1…150
High range lx 20…1000
Hysteresis (switching Off/On ratio) 1.25 Δ=3lx
Delay time: switching On / Off s 15/30 25/50
Ambient temperature range °C –20…+50 –20…+50
Protection category:
light dependent relay/light sensor IP 20/IP 54 IP 20/IP 54
Approvals (according to type)
II-2018www.findernet.com
11 SERIES
Light dependent relays 12 - 16A
11
SERIES