Datasheet

22.32.0.xxx.1xx0 22.32.0.xxx.4xx0
1
2 NO, 3 mm * (or 1 NO + 1 NC or 2 NC)
25 / 80 25 / 120
250 / 440 250 / 440
6,250 6,250
10 10
1,800 1,800
11
—10
2,000
200
800
500
25/5/1 25/5/1
1,000 (10 / 10) 1,000 (10 / 10)
AgNi AgSnO
2
12 - 24 - 48 - 60 - 120 - 230 12 - 24 - 48 - 60 - 120 - 230
2 /2.2 2 / 2.2
(0.8 …1.1) U
N
(0.8 …1.1) U
N
0.4 U
N
0.4 U
N
0.1 U
N
0.1 U
N
2 · 10
6
2 · 10
6
70 · 10
3
30 · 10
3
30 / 20 30 / 20
66
–20…+50 –20…+50
IP20 IP20
Contact specification
Contact configuration
Rated current/Maximum peak current A
Rated voltage V AC
Rated load AC1 / AC-7a (per pole @ 250 V) VA
Rated current AC3 / AC-7b A
Rated load AC15 (per pole @ 230 V) VA
Single-phase motor rating (230 V AC) kW
Rated current AC-7c A
230 V lamps rating: incandescent or halogen W
compact fluorescent (CFL) W
electronic ballast fluorescent tubes W
electromagnetic ballast compens. fluorescent tubes W
Breaking capacity DC1: 30/110/220 V A
Minimum switching load mW (V/mA)
Contact material
Coil specification
Nominal voltage (U
N
) V DC/AC (50/60 Hz)
Rated power AC/DC VA (50 Hz)/W
Operating range DC/AC (50/60 Hz)
Holding voltage DC/AC (50/60 Hz)
Must drop-out voltage DC/AC (50/60 Hz)
Technical data
Mechanical life AC/DC cycles
Electrical life at rated load AC-7a cycles
Operate/release time ms
Insulation between coil and contacts (1.2/50 μs)
kV
Ambient temperature range °C
Protection category
Approvals (according to type)
AgNi contacts, specifically
intended for resistive and
slightly inductive loads as
well as for motor loads
AgSnO
2
contacts, specifically
intended for lamp loads and
for high inrush current loads
Features
25 A modular contactor - 2 pole
17.5 mm wide
NO contact gap ≥ 3 mm, double break
Continuous duty for the coil and contacts
AC/DC silent coil (with varistor protection)
Protective separation (reinforced insulation)
between coil and contacts
Mechanical and LED indicators as standard
Auto-On-Off selector version available
AgNi and AgSnO
2
contact versions available
Compliant with EN 61095: 2009
Auxiliary contact module available,
quick-assembly with the main contactor
(1 NO + 1 NC and 2 NO versions)
35 mm rail (EN 60715) mount
22 Series - Modular contactors 25 A
22.32...1xx0 / 22.32...4xx0
Screw terminal
* Contact gap ≥ 3 mm for NO contacts only;
NC contacts ≥ 1.5 mm
For outline drawings see page 7
2 NO 1 NO + 1 NC 2 NC
(x3x0) (x5x0) (x4x0)
II-2013, www.findernet.com

Summary of content (10 pages)