A
60 SERIES
General purpose relays 6 - 10A
60
SERIES
Plug-in mount - 6A
Bifurcated contacts for low level switching
Type 60.12 - 52xx
- 2 pole, 6 A
Type 60.13 - 52xx
- 3 pole, 6 A
• 2 & 3 pole changeover contacts
• Cadmium Free contacts
(Gold plated Silver Nickel)
• AC coils & DC coils
• Lockable test button with mechanical flag
indicator (preferred version)
• 90 series sockets
• Coil EMC suppression
• Timer accessories 86 series
• European Patent
For UL ratings see:
“General technical information” page V
60.12 - 52xx 60.13 - 52xx
• 2 pole, 6A
• Bifurcated contacts with AgNi + Au
• 8 pin plug-in
• 3 pole, 6A
• Bifurcated contacts with AgNi + Au
• 11 pin plug-in
For outline drawing see page 8
Contact specification
Contact configuration 2 CO (DPDT) 3 CO (3PDT)
Rated current/Maximum peak current A 6/10 6/10
Rated voltage/
Maximum switching voltage VAC 250/400 250/400
Rated load AC1 VA 1500 1500
Rated load AC15 (230VAC) VA 250 250
Single phase motor rating (230VAC) kW 0.185 0.185
Breaking capacity DC1: 30/110/220V A 6/0.3/0.12 6/0.3/0.12
Minimum switching load mW (V/mA) 50 (5/5) 50 (5/5)
Standard contact material AgNi + Au AgNi + Au
Coil specification
Nominal voltage (U
N
) VAC (50/60Hz) 6 - 12 - 24 - 48 - 60 - 110 - 120 - 230 - 240 - 400
VDC 6 - 12 - 24 - 48 - 60 - 110 -125 - 220
Rated power AC/DC VA (50Hz)/W 2.2/1.3 2.2/1.3
Operating range AC (0.8…1.1)U
N
(0.8…1.1)U
N
DC (0.8…1.1)U
N
(0.8…1.1)U
N
Holding voltage AC/DC 0.8U
N
/0.5U
N
0.8U
N
/0.5U
N
Must drop-out voltage AC/DC 0.2U
N
/0.1U
N
0.2U
N
/0.1U
N
Technical data
Mechanical life AC/DC cycles 20·10
6
/50·10
6
20·10
6
/50·10
6
Electrical life at rated load AC1 cycles 250·10
3
250·10
3
Operate/release time ms 11/4 11/4
Insulation between coil
and contacts (1.2/50μs) kV 4 3.6
Dielectric strength
between open contacts VAC 1000 1000
Ambient temperature range °C –40…+70 –40…+70
Environmental protection RT I RT I
Approvals (according to type)