Data Sheet
Three-phase
Multifunction energy meter 
Bi-directional, MID certified with Ethernet 
Modbus TCP integrated interface and backlit 
LCD display for 4 wire systems
Type 7E.78.8.400.0410: 
Direct connection up to 80A 
Type 7E.86.8.400.0410: 
6A direct installation, up to 50 000 A using 
current transformer 
• Display of total or partial (resettable) energy 
consumption: kWh, kVAh or kvarh - for the total 
system or per phase
• Scroll to view the following instantaneous 
values: V, A, PF, kW, kVA, kvar, Hz and direction 
of power flow
• Fault indication in the event of loss or incorrect 
phase sequence 
• 8 digit backlit LCD display
• Ethernet Modbus TCP integrated 
communications port
• Programmable** SO pulse output for remote 
energy monitoring according to EN62053-31
• Active power accuracy Class B according to 
EN50470-3
• Reactive power accuracy Class 2 according to 
EN62053-23
• Protection category II
• Accessories: sealable terminal cover tamper
• 35mm rail (EN60715) mount
*  Minimum CT ratio: 1:1 
Maximum CT ratio: 10 000:1 
CT secondary programmable: 1 or 5A
**  SO output can be associate with kWh, kVAh or 
kvarh.
7E.78.8.400.0410 7E.86.8.400.0410
• Reference current 5A (80A Maximum)
• Ethernet Modbus TCP integrated interface
• Three-phase systems - 4 wire
• Reference current 1A (6A Maximum)
• Ethernet Modbus TCP integrated interface
• Three-phase systems - 4 wire
• Usable with current transformer*
• Full scale (FSA) programmable*
3 x 230/400 V
AC 50/60 Hz
SO
+24V
ETHERNET
3 x 230/400 V
AC 50/60 Hz
ETHERNET
SO
+24V
For outline drawing see page 16
Specification
Reference/Maximum current I
n
/I
max
 A 5/80 1/6
Starting current I
st
 A 0.02 0.002
Minimum measured current I
min
 A 0.25 0.01
Current range (within accuracy class)  A 0.5…80 0.05…6
Maximum peak current  A 2400 (10ms) 120 (500ms)
Supply (& monitored) voltage U
N
 VAC 3 x 230/400…3 x 240/415 3 x 230/400…3 x 240/415
Operating range (0.8…1.2)U
N
(0.8…1.2)U
N
Frequency  Hz 50/60 50/60
Power consumption per phase  W/VA ≤1/3.5 ≤1/3.5
CT burden (per phase)  VA — 0.04
Display Eight digit counter - backlit LCD display
Max. totalising count/Min. increment  kWh 999999.99/0.01 999999.99/0.01
LED pulses per kWh 1000 10 000
LED pulse length  ms 10±0.5 10±0.5
Ethernet technical data
Bus system Ethernet TCP Ethernet TCP
Protocol Modbus TCP, HTTP, NTP; DHCP  Modbus TCP, HTTP, NTP; DHCP 
Conforms to standard IEEE 802.3 IEEE 802.3
Communication speed  Mbps 10/100 10/100
Open collector- output specification (SO+/SO–)
Number/Type 1 opto-isolated output 1 opto-isolated output
Voltage range/Maximum current
(conform to EN62053-31)  VDC/mA 3.3…27/1…27 3.3…27/1…27
Pulses per kWh**  Imp/kWh** 100 See table page 13
Pulse length  ms 50 ± 2 50 ± 2
Technical data
Accuracy class B B
Ambient temperature (Within accuracy class)  °C –25…+55 –25…+55
Protective class II II
Protection category: Housing/terminals IP50/IP20 IP50/IP20
Approvals (according to type)
V-2018, www.findernet.com
11
E
7E
SERIES 
7E SERIES 
Energy meters