Data Sheet

Three-phase
Multifunction energy meter
Bi-directional, MID certified with Ethernet
Modbus TCP integrated interface and backlit
LCD display for 4 wire systems
Type 7E.78.8.400.0410:
Direct connection up to 80A
Type 7E.86.8.400.0410:
6A direct installation, up to 50 000 A using
current transformer
Display of total or partial (resettable) energy
consumption: kWh, kVAh or kvarh - for the total
system or per phase
Scroll to view the following instantaneous
values: V, A, PF, kW, kVA, kvar, Hz and direction
of power flow
Fault indication in the event of loss or incorrect
phase sequence
8 digit backlit LCD display
Ethernet Modbus TCP integrated
communications port
Programmable** SO pulse output for remote
energy monitoring according to EN62053-31
Active power accuracy Class B according to
EN50470-3
Reactive power accuracy Class 2 according to
EN62053-23
Protection category II
Accessories: sealable terminal cover tamper
35mm rail (EN60715) mount
* Minimum CT ratio: 1:1
Maximum CT ratio: 10 000:1
CT secondary programmable: 1 or 5A
** SO output can be associate with kWh, kVAh or
kvarh.
7E.78.8.400.0410 7E.86.8.400.0410
Reference current 5A (80A Maximum)
Ethernet Modbus TCP integrated interface
Three-phase systems - 4 wire
Reference current 1A (6A Maximum)
Ethernet Modbus TCP integrated interface
Three-phase systems - 4 wire
Usable with current transformer*
Full scale (FSA) programmable*
3 x 230/400 V
AC 50/60 Hz
SO
+24V
ETHERNET
3 x 230/400 V
AC 50/60 Hz
ETHERNET
SO
+24V
For outline drawing see page 16
Specification
Reference/Maximum current I
n
/I
max
A 5/80 1/6
Starting current I
st
A 0.02 0.002
Minimum measured current I
min
A 0.25 0.01
Current range (within accuracy class) A 0.5…80 0.05…6
Maximum peak current A 2400 (10ms) 120 (500ms)
Supply (& monitored) voltage U
N
VAC 3 x 230/400…3 x 240/415 3 x 230/400…3 x 240/415
Operating range (0.8…1.2)U
N
(0.8…1.2)U
N
Frequency Hz 50/60 50/60
Power consumption per phase W/VA ≤1/3.5 ≤1/3.5
CT burden (per phase) VA 0.04
Display Eight digit counter - backlit LCD display
Max. totalising count/Min. increment kWh 999999.99/0.01 999999.99/0.01
LED pulses per kWh 1000 10 000
LED pulse length ms 10±0.5 10±0.5
Ethernet technical data
Bus system Ethernet TCP Ethernet TCP
Protocol Modbus TCP, HTTP, NTP; DHCP Modbus TCP, HTTP, NTP; DHCP
Conforms to standard IEEE 802.3 IEEE 802.3
Communication speed Mbps 10/100 10/100
Open collector- output specification (SO+/SO–)
Number/Type 1 opto-isolated output 1 opto-isolated output
Voltage range/Maximum current
(conform to EN62053-31) VDC/mA 3.3…27/1…27 3.3…27/1…27
Pulses per kWh** Imp/kWh** 100 See table page 13
Pulse length ms 50 ± 2 50 ± 2
Technical data
Accuracy class B B
Ambient temperature (Within accuracy class) °C –25…+55 –25…+55
Protective class II II
Protection category: Housing/terminals IP50/IP20 IP50/IP20
Approvals (according to type)
V-2018, www.findernet.com
11
E
7E
SERIES
7E SERIES
Energy meters