Data Sheet

X-2017, www.findernet.com
B
Additional technical data - Timed Interface Module
EMC specifications
Type of test Reference standard
Electrostatic discharge contact discharge EN61000-4-2 4kV
air discharge EN61000-4-2 8kV
Radio-frequency electromagnetic field (80÷1000MHz) EN61000-4-3 10V/m
Fast transients (burst) (5-50ns, 5kHz) on Supply terminals EN 61000-4-4 4kV
Surges (1.2/50µs) on Supply terminals common mode EN61000-4-5 4kV
differential mode EN61000-4-5 4kV
Radio-frequency common mode (0.15÷80MHz) on Supply terminals EN61000-4-6 10V
Radiated and conducted emission EN55022 class B
Other data EMR SSR
Power lost to the environment without contact current W 0.1 0.1
with rated current W 0.6 0.5
Terminals 38.21
Wire strip length mm 10
Screw torque
Nm 0.5
Max. wire size solid cable stranded cable
mm
2
1x2.5 / 2x1.5 1x2.5 / 2x1.5
AWG 1x14 / 2x16 1x14 / 2x16
Times scales
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
(0.1…3)s
(3…60)s
(1…20)min
(0.3…6)h
Functions
LED Supply voltage NO contact/output
OFF Open
ON Open (time in progress)
ON Closed
Wiring diagram U = Supply voltage = Output contact
1 2 3 4
(AI) On-delay.
Apply power to timer.
Output contacts transfer after preset time has elapsed.
Reset occurs when power is removed.
1 2 3 4
(DI) Interval.
Apply power to timer.
Output contacts transfer immediately.
After the preset time has elapsed, contacts reset.
1 2 3 4
(GI) Pulse delayed.
Apply power to timer. Output contacts transfer after
preset time has elapsed. Reset occurs after a fixed time
of 0.5s.
1 2 3 4
(SW) Symmetrical flasher (starting pulse on).
Apply power to timer.
Output contacts transfer immediately and cycle
between ON and OFF for as long as power is applied.
The ratio is 1:1 (time on= time off).
12
38 SERIES
Timed interface modules
38