Datasheet

5
12
SERIES
12 SERIES
Time switches 16 A
J
VII-2023, www.findernet.com
Digital time switch, weekly programming
- Can be programmed in “Classic” mode
via the joystick, or “Smart” mode via
smartphones with NFC communication
Type 12.61
- 1 CO 16A
Type 12.62
- 2 CO 16A
Functions:
Switch ON, Switch OFF
Pulse: 1s…59min
Minimum time interval setting - 1 minute
Summer/Winter European, Australian, Brazilian time
LCD status indication, set-up and programming
Lock with a 4-digit PIN
Back-light display
Internal battery for set-up and programming
without supply, easily replaceable from the front
Protective separation between supply and
contacts
35mm wide
35mm rail (EN60715) mount
Cadmium free contact material
12.61 12.62
Weekly programming
1 CO 16A
Switch ON, Switch OFF, Pulse
Weekly programming
2 CO 16A
Switch ON, Switch OFF, Pulse
For outline drawing see page 16
Contact specification
Contact configuration 1 CO (SPDT) 2 CO (DPDT)
Rated current/Maximum peak current A 16/30 (120A - 5ms) 16/30 (120A - 5ms)
Rated voltage/
Maximum switching voltage VAC 250/400 250/400
Rated load AC1 VA 4000 4000
Rated load AC15 (230VAC) VA 750 750
Nominal lamp rating:
230V incandescent/halogen W 2000 2000
fluorescent tubes with
electronic ballast W 1000 1000
fluorescent tubes with
electromagnetic ballast W 750 750
CFL W 400 400
230V LED W 400 400
LV halogen or LED with
electronic ballast W 400 400
LV halogen or LED with
electromagnetic ballast W 800 800
Minimum switching load mW (V/mA) 1000 (10/10) 1000 (10/10)
Standard contact material AgSnO
2
AgSnO
2
Supply specification
Nominal voltage (U
N
) VAC (50/60Hz) 12…24 110…230 110…230
VDC 12…24 110…230 110…230
Rated power AC/DC VA (50Hz)/W 2.8/0.9 2.8/0.9
Operating range VAC (50Hz) 10…30 88…253 88…253
VDC 10…30 88…253 88…253
Technical data
Electrical life at rated load in AC1 cycles 100·10
3
100·10
3
Type of time switch Weekly Weekly
Memory locations for switching times 50 50
Minimum internal setting min 1 1
Accuracy s/day 1 1
Communication protocol NFC NFC
Ambient temperature range °C –20…+50 (see page 10,
diagram L12)
–20…+50 (see page 10,
diagram L12)
Protection category IP 20 IP 20
Approvals (according to type)
E
U
R
O
P
E
A
N
E
U
R
O
P
E
A
N
PATENT
E
U
R
O
P
E
A
N
E
U
R
O
P
E
A
N
PATENT