Datasheet

12 Series - Time switches 16 A
Technical data
Insulation 12.01, 12.11, 12.31 12.21, 12.22, 12.71, 12.91, 12.92
Dielectric strength between open contacts V AC
1,000 1,000
Other data 12.01, 12.11, 12.31 12.21, 12.22, 12.71, 12.91, 12.92
Power back-up 100 h (following 80 h continuous energisation) 6 years
Power lost to the environment
without contact current W 1.5 2
with rated current W 2.5 3 (for 1 pole) 4 (for 2 pole)
Screw torque Nm 1.2 1.2
Max. wire size solid cable stranded cable solid cable stranded cable
mm
2
1x6 / 2x4 1x6 / 2x2.5 1x6 / 2x4 1x6 / 2x2.5
AWG 1x10 / 2x12 1x10 / 2x14 1x10 / 2x12 1x10 / 2x14
6
Technical data type 12.51 and 12.81
Insulation Dielectric strength Impulse (1.2/50 µs)
between supply and contacts 4,000 V AC 6 kV
between open contacts 1,000 V AC 1.5 kV
EMC specifications
Type of test Reference standard
Electrostatic discharge contact discharge EN 61000-4-2 4 kV
air discharge EN 61000-4-2 8 kV
Radiated electromagnetic field (80 … 1,000 MHz) EN 61000-4-3 10 V/m
Fast transients (burst 5/50 ns, 5 and 100 kHz) EN 61000-4-4 4 kV
Voltage pulses on supply terminals common mode EN 61000-4-5 4 kV
(surge 1.2/50 µs) differential mode EN 61000-4-5 4 kV
Radiofrequency common mode voltage (0.15…80 MHz) EN 61000-4-6 10 V
Voltage dips 70 % U
N
, 40 % U
N
EN 61000-4-11 10 cycles
Short interruptions EN 61000-4-11 10 cycles
Radio frequency conducted emissions 0.15…30 MHz EN 55014 class B
Radiated emissions 30…1,000 MHz EN 55014 class B
Terminals
Screw torque 0.8 Nm
Max. wire size solid cable 1 x 6 / 2 x 4 mm
2
1 x 10 / 2 x 12 AWG
stranded cable 1 x 4 / 2 x 2.5 mm
2
1 x 12 / 2 x 14 AWG
Wire strip length 9 mm
Other data
Power back-up (Battery life) 6 years
Battery type CR 2032, 3 V, 230 mAh
Power lost to the environment
in stand-by 1.4 W
without contact current 2.9 W
with rated current 3.5 W
XII-2012, www.findernet.com