Datasheet
VI-2015, www.findernet.com
1
K
13
SERIES
13 SERIES
Electronic step relays 10 - 16A
13.81 - Electronic step relay - Rail mount - 1 Pole
13.91 - Electronic step relay and timing step relay
Switch box mount - 1 Pole
• Fixed time (10minutes) timing function
selectable (13.91)
• Use with 3 or 4 wire connection, with automatic
recognition by the relay
• Control input can be continuously applied
• Longer mechanical and electrical life, and much
quieter than electromechanical step relays
• “Zero crossing” load switching
• Can be mounted behind blanking plates, as
widely used in residential wiring systems such
as; BTicino: Axolute, Matix, Living and Magic,
Gewiss: GW24, Vimar: Plana and Idea…(13.91)
• 35mm rail (EN60715) mount (13.81)
• Cadmium free contact material
13.81/91
Screw terminals
13.81 13.91
• 1 NO (SPST-NO)
• 35mm rail (EN60715) mount
• 17.5mm wide
• 1 NO (SPST-NO)
• Step relay and timing step
relay (10minutes)
• For mounting within
residential switch boxes
For outline drawing see page 10
Contact specification
Contact configuration 1 NO (SPST-NO) 1 NO (SPST-NO)
Rated current/Maximum peak current A 16/30 (120 - 5ms) 16/20 (80 - 5ms)
Rated voltage/
Maximum switching voltage VAC 230/— 230/—
Rated load AC1 VA 3700 2300
Rated load AC15 (230VAC) VA 750 450
Nominal lamp rating:
230V incandescent/halogen W 3000 1000
fluorescent tubes with
electronic ballast W 1500 500
fluorescent tubes with
electromechanical ballast W 1000 350
CFL W 600 300
230V LED W 600 300
LV halogen or LED with
electronic ballast W 600 300
LV halogen or LED with
electromechanical ballast W 1500 500
Minimum switching load mW (V/mA) 1000 (10/10) 1000 (10/10)
Standard contact material AgSnO
2
AgSnO
2
Supply specification
Nominal voltage (U
N
) VAC (50/60Hz) 230 230
VDC — —
Rated power VA (50Hz)/W 3/1.2 2/1
Operating range AC (50Hz) (0.8…1.1)U
N
(0.8…1.1)U
N
DC — —
Technical data
Electrical life at rated load in AC1 cycles 100·10
3
100·10
3
Maximum impulse duration continuous continuous
Dielectric strength between: open contacts VAC 1000 1000
supply - contacts VAC — —
Ambient temperature range °C –10…+60 –10…+50
Protection category IP 20 IP 20
Approvals (according to type)