Datasheet

VI-2015, www.findernet.com
5
K
13
SERIES
13 SERIES
Electronic step/monostable and call/reset
Functions
Type
13.01
Monostable
On closure of a switch between terminals (B2-B3) the output
contact will close, and remain so, until the switch opens.
Step relay (bistable)
After every impulse (B1-B2), the output contact changes state -
alternately switching from open to closed and vice versa.
13.11
13.12
(13.12 only)
Call and Reset relay
On momentary closure of the Set switch (S), the output contact
closes. Only a momentary closure of the Reset switch (R) will
open the output contact.
13.81
(RI) Step relay
After every impulse, the output contact changes state -
alternately switching from open to closed and vice versa.
13.91
(RI) Step relay
After every impulse, the output contact changes state -
alternately switching from open to closed and vice versa.
(IT) Timing step relay
On initial impulse the output contact closes and timing starts
for the pre-set duration (fixed 10min); On expiry of the time
delay, the output contact opens.
During the timing period it is possible to immediately open the
contact with a further impulse.
Operating mode setup for type 13.91
RI IT
a) Remove the supply voltage
b) Press the control button
c) Apply the supply to the relay, keeping the button closed.
After 3 second, the light will flash twice to indicate the
selection of the “IT function, or flash once for “RI” function.
IT RI