Data Sheet

XI-2017, www.findernet.com
5
K
13
SERIES
13 SERIES
Electronic call/reset relays and monostable relays 8 - 12A
13.11 - Call & Reset Relay - Rail mount - 1 Pole
13.12 - Call & Reset Relay - Rail mount - 2 Pole
13.31 - Electromechanical monostable relay
Switch box mount - 1 Pole
Call relay with reset command suitable for
residential and commercial applications: public
bathroom, hospital, hotel (type 13.11/13.12)
Can be mounted behind blanking plates, as
widely used in residential wiring systems such
as; BTicino: Axolute, Matix, Living e Magic,
Gewiss: GW24, Vimar: Plana e Idea…(13.31)
35mm rail (EN60715) or flange mount
(13.11 and 13.12)
Cadmium free contact material (13.31)
13.11/12/31
Screw terminals
13.11 13.12 13.31
1 CO (SPDT)
Call relay with reset command
35mm rail (EN60715) mount
17.5mm wide
1 CO (SPDT) + 1 NO (SPST-NO)
Call relay with reset command
35mm rail (EN60715) mount
17.5mm wide
1 NO (SPST-NO)
Interposing monostable relay
For mounting within
residential switch boxes
* During impulse only.
For outline drawing see page 12
Contact specification
Contact configuration 1 CO (SPDT) 1 CO (SPDT) + 1 NO (SPST-NO) 1 NO (SPST-NO)
Rated current/Maximum peak current A 12/30 8/15 12/20 (80A - 5ms)
Rated voltage/
Maximum switching voltage VAC 250/400 250/400 250/400
Rated load AC1 VA 3000 2000 3000
Rated load AC15 (230VAC) VA 750 400 450
Nominal lamp rating:
230V incandescent/halogen W 1200 800 800
fluorescent tubes with
electronic ballast W 500 300 400
fluorescent tubes with
electromechanical ballast W 400 250 300
CFL W 300 150 200
230V LED W 300 150 200
LV halogen or LED with
electronic ballast W 300 150 200
LV halogen or LED with
electromechanical ballast W 500 300 400
Minimum switching load mW (V/mA) 500 (5/5) 300 (5/5) 1000 (10/10)
Standard contact material AgCdO AgCdO AgSnO
2
Supply specification
Nominal voltage (U
N
) VAC (50/60Hz) 230…240 12 - 24 12 - 230
VDC 12 - 24 24
Rated power AC/DC V A (50Hz)/W 1.7/0.7* 3/2.5* 1/0.4
Operating range AC (50Hz) (0.8…1.1)U
N
(0.8…1.1)U
N
(0.8…1.1)U
N
DC (0.8…1.1)U
N
(0.8…1.1)U
N
Technical data
Electrical life at rated load in AC1 cycles 100·10
3
100·10
3
70 · 10
3
Maximum impulse duration 10s (100ms minimum) 10s (100ms minimum) continuous
Dielectric strength between: open contacts VAC 1000 1000 1000
supply - contacts VAC 2000 2000 2000
Ambient temperature range °C –10…+60 –10…+60 –10…+60
Protection category IP 20 IP 20 IP 20
Approvals (according to type)