Datasheet

15
SERIES
15 Series - Dimmer
1
I-2015, www.findernet.com
I
“Master + slave” system for multiple load
dimming
Suitable for incandescent and halogen lighting
loads (with or without transformer or electronic
supply)
Compatible with energy saving (CFL or
LED) dimmable lamps and with all types of
electromagnetic transformers
0-10V driving. Master Dimmer Type 15.10 is
able to drive up to 32 Slaves Dimmer Type 15.11
Use with 4 wire connection
“Soft On and Off transitions
Selectable operating modes with or without
previous light level memory (15.10)
Staircase timer function, with “switch-off early
warning” signalled by lamps dimming (15.10)
Linear dimming
Thermal protection against overload, thermo-
fuse for extreme protection and short-circuit
protection (15.11)
230VAC supply, 50/60Hz with automatic
recognition of frequency
Screw terminal
15.10 15.11
“Master” dimmer
0-10V/1-10V output, usable
both for driving one or more
15.11, or for directly controlling
Drivers and luminaires with
0-10V/1-10V inputs
Multi-function (with or without
memory, including specific
“memory for CFL function)
Dimming speed setting
Staircase timer function, with
switch-off early warning”
signalled by lamps dimming
6A output relay contact*
17.5mm wide, modular
“Slave dimmer
1-10V input, driven by 15.10 or
by other 0-10V/1-10V output
devices
Maximum lamp load 400W
100W load with energy saving
dimmable lamps (LED and CFL)
Leading and trailing edge
dimming methods
Transformer function (for
use with electromechanical
transformers)
Minimum dimming level
setting
17.5mm wide, modular
* When the total load exceeds 6A, it is necessary
to switch it through an external contactor
For outline drawing see page 9
“Master Dimmer” output specifications
Driving signal (Output mode automatically
configures to match input mode of the
connected Driver)
0-10V, +35mA max
(Active current sourcing mode)
1-10V, –35mA max
(Passive current sinking mode)
Contact configuration A 1 NO (6A/230VAC)*
“Slave Dimmer” output specifications
Power max. W 400
Power min. W 3
Nominal lamp ratings:
230V incandescent or halogen W
400
(1)
Toroidal electromagnetic transformers
for LV halogen W 400
(2)
E-core electromagnetic transformers
for LV halogen W 400
(2)
Electronic transformers (ballasts)
for LV halogen W 400
(1)
Dimmable compact fluorescent (CFL) W 100
(3)
Dimmable 230V LED W 100
(3) or (1)
Dimmable electronic transformers
for LV LED W 100
(1)
Supply specifications
Nominal voltage (U
N
) VAC (50/60Hz) 110…230 230
Operating range (0.8…1.1)U
N
(0.8…1.1)U
N
Stand-by power consumption W 0.5 0.5
Dimming operating modes
Trailing edge (
)
Leading edge ( ) and ( )
Technical data
Dimming speed (total dimming time) s 1.5…10
Delay setting (staircase function) min 0.5…20
Max no. of illuminated push-button (≤1mA) 15
Ambient temperature range °C –10…+50 –10…+50
(4)
Protection category IP 20 IP 20
Approvals (according to type)
Note
(1)
Select trailing edge” ( ) position on the front selector.
(2)
Select “transformer ( ) position on the front selector. Preferably, no more than 2 transformers.
(3)
Select leading edge ( ) position on the front selector, and set the appropriate minimum dimming value (dependent on lamp type).
(4)
With lamp load >300W (>75W for CFL or LED lamps), adequate ventilation must be provided - a gap of 9mm on both side of the dimmer is
suggested. Use the plastic separator type 022.09.

Summary of content (10 pages)