Data Sheet
5
2 NO (DPST-NO)
5/15 A
250/400 V AC
1,250 VA
250 VA
0.185 kW
3/0.35/0.2 A
500 mW (10 V/5 mA)
AgCdO
1 NO (SPST-NO)
100 mA/10 mA
24 V
24 V
24 V
1.6 VA (50 Hz)/0.8 W
(0.8…1.1) U
N
(0.8…1.1) U
N
–20…+50 °C
IP20
Output specification (terminals 13-14-24)
Contact configuration
Rated current/Maximum peak current I
N
/I
max
Rated voltage/Maximum switching voltage U
N
/U
max
Rated load AC1
Rated load AC15
Single phase motor rating (230 V AC)
Breaking capacity DC1 (24/110/220 V)
Minimum switching load
Standard contact material
Feedback output specification (terminals 51-52)
Contact configuration
Maximum / Minimum current
Rated voltage AC/DC
Supply & Input specification
Nominal voltage U
N
AC (50/60 Hz)
U
N
DC
Rated power P
N
Operating range V AC
V DC
Ambient temperature range
Protection category
19 Series - Override & Status indicating modules
Features
Override module - Auto/Off/Low/High
• Override output module intended to permit the
automatic control of two-speed pumps, blowers
or motor groups. Or, in the case of installation,
maintenance or failure, to permit the load
equipment to be turned “Off“ or to run in “Low
speed“ or “High speed“ under “Hand“ control
• 4 function selector switch:
- Auto: directly controlled by the BMS or PLC
- Off: relays permanently Off
- Hand Low: Low speed relay output
permanently On
- Hand High: High speed relay output
permanently On
• 24V AC/DC supply and module inputs
• 35 mm rail (EN 60715) mounting
Application examples:
• control of two-speed pumps, blowers or motor
groups commonly associated with building
management systems
• Low and High output contacts
• 1 feedback output contact
• 35 mm wide
• LED indicator
19.42.0.024.0000
Wiring diagram
In position “Low”, “High” or “O” (Off) a Yellow LED will flash and the feedback output
(51-52) will open to indicate that the module is not in the “A” (Automatic) position.
Note: If inputs A3 and A4 are on together, A4 takes precedence, and only High output
(13-24) is closed.
Note 1: the operating delay time from opening of contact13-14 and closing of contact 13-24 is about 80 ms, both in Auto position (when the in-put is switched from
A3 to A4) and when the selector is switched from Low to High position.
Note 2: as a consequence, the maximum switching frequency of the output is 3 Hz.
Note 3: In the case of high inertia loads it may be necessary to add a Timer relay to delay the energisation of the Low speed motor contactor (following High speed
running), to allow the motor time to decelerate.
For outline drawing see page 11