Data Sheet
B
Auto/Off/On output module 10A
• Auto/Off/On output module intended to
permit the automatic control of pumps,
blowers or motor groups. Or, in the case of
installation, maintenance or failure, to permit
the load equipment to be turned “Off“ or
turned “On“
• Ideal interface for PLC and electronic systems
• Only 11.2mm wide
• 3 function selector switch:
- Auto: works as a monostable relay
(following A3 input)
- Off: relay permanently OFF
- On: relay permanently ON
• 24VAC/DC supply and module input
• 35mm rail (EN60715) mounting
Application examples:
• control of pumps, blowers or motor groups
• primarily suited to Industrial control systems
Wiring diagram
Controller, PLC Type 19.21
19.21.0.024.0000
• 1 CO output contact
• 11.2mm wide
• Feedback contact
Auto-Operation Intervention-(Manual-)Operation
Switch position:
Request
Response
LED Signals
B1-B2 feedback to the controller signaling Auto-operation
A3-A2 “Auto“ signal from Controller
For outline drawing see page 9
Contact specification
Contact configuration 1 CO (SPDT)
Rated current/Maximum peak current
A
10/15
Rated voltage/
Maximum switching voltage VAC 250/400
Rated load AC1
VA
2500
Rated load AC15 (230VAC)
VA
500
Single phase motor rating (230VAC)
kW
0.44
Breaking capacity DC1 (24/110/220V)
A
10/0.3/0.12
Minimum switching load
mW (V/mA)
300 (5/5)
Standard contact material AgSnO
2
Feedback contact specification (terminals B1-B2)
Contact configuration 1 NO (SPST-NO)
Maximum current
mA
300
Rated voltage VAC/DC 24
Supply & Input specification
Nominal voltage (U
N
) VAC (50/60Hz) 24
VDC 24
Rated power VA (50Hz)/W 0.6/0.4
Operating range AC (0.8…1.1)U
N
DC (0.8…1.1)U
N
Technical data
Ambient temperature range °C –20…+50
Protection category IP 20
Approvals (according to type)
X-2017, www.findernet.com
3
19
SERIES
19 SERIES
Relay actuators & Status indicating modules