Data Sheet
B
Analogue override module - Auto/Hand
(0…10)V
• Analogue output module intended to provide,
by the selection switch on the front panel, a
(0…10)V output, automatically or by hand.
• With the selector switch in position “A“
(Automatic) the (0…10)V signal is derived
from the controller.
In position “H” (Hand) the controller signal is
ignored and the (0…10)V signal is derived
directly from the potentiometer setting on the
facia of the module
• The level of the (0…10)V output signal is
displayed by 3 green LEDs, set at >25%, >50%
and >75%.
• 24VAC/DC supply
• 35mm rail (EN60715) mounting
Application examples:
• permits the direct control of proportional
valves under exceptional circumstances or
where the automatic controller has failed
Wiring diagram
Controller, PLC Type 19.50
19.50.0.024.0000
• Analogue output (0…10)V,
plus 1 feedback output contact
• 17.5mm wide
• LED indicator
Auto-Operation Intervention-(Manual-)Operation
Request
Response
LED Signals
Switch position:
53-54 feedback to the controller signaling Auto-operation
Y
in
-A2 variable (0…10)VDC from the controller
Hand (0…10)V DC value set by the potentiometer
For outline drawing see page 9
(0…10)V Signal specification (terminal Y-in)
Input control signal VDC 0…10 (Imax 20mA - short-circuit protected)
Green LED 25% >2.5V
Green LED 50% >5V
Green LED 75% >7.5V
Feedback output specification (terminals 53-54)
Output configuration 1 NO (SPST-NO)
Maximum / Minimum current mA 100/10
Rated voltage VAC/DC 24
Supply & Input specification
Nominal voltage (U
N
) VAC (50/60Hz) 24
V
DC 24
Rated power AC/DC VA (50Hz)/W 0.9/0.7
Operating range AC (0.8…1.1)U
N
DC (0.8…1.1)U
N
Technical data
Ambient temperature range °C –20…+50
Protection category IP 20
Approvals (according to type)
X-2017, www.findernet.com
4
19 SERIES
Relay actuators & Status indicating modules
19
SERIES