Data Sheet
8
19 Series - Override & Status indicating modules
Ordering information
Example: 19 series Auto/Off/Hand override module, 1 CO (SPDT) 5 A contact, 24 V AC/DC supply.
Contact material
0= Standard for 19.21/31/32/41/42/50
4= Standard for 19.91
Codes / Module width
19.21.0.024.0000 / 11.2 mm
19.31.0.024.0000 / 17.5 mm
19.32.0.024.0000 / 17.5 mm
19.41.0.024.0000 / 17.5 mm
19.42.0.024.0000 / 35.0 mm
19.50.0.024.0000 / 17.5 mm
19.91.9.012.4000 / 17.5 mm
19.91.9.024.4000 / 17.5 mm
Series
Type
21= Auto/Off/On output module, 11.2mm
31= 1-channel status indicating module
32= 2-channel status indicating module
41= Override module - Auto/Off/Hand
42= Override module - Auto/Off/Low/High
50= Analogue override module (0…10) V
91= Power relay module
Supply version
0 = AC (50/60 Hz) / DC
9 = DC
Supply voltage
012 = 12 V
024 = 24 V
4 1 0 00 0 0
... .
02419
Insulation 19.21 19.31/32 19.41/42 19.50 19.91
Dielectric strength (V AC) between supply and contacts 3,000 1,000 2,000 — 4,000
between open contacts 1,000 750 1,000 — 1,000
between supply and feedback output 2,000 — 1,500 1,500 —
EMC specifications
Type of test Reference standard 19.21/31/32/42/91 19.41/50
Electrostatic discharge contact discharge EN 61000-4-2 4 kV
air discharge EN 61000-4-2 8 kV
Radiated electromagnetic field (80 … 1,000 MHz) EN 61000-4-3 30 V/m
Fast transients (burst) (5-50 ns, 5 kHz) EN 61000-4-4 4 kV
Voltage pulses (1.2/50 µs) common mode EN 61000-4-5 2 kV 1 kV
on supply terminals differential mode EN 61000-4-5 1 kV 0.5 kV
Terminals 19.21 19.31/32/41/42/91
Screw torque 0.5 Nm 0.8 Nm
Max. wire size solid cable 1x6/2x2.5 mm
2
1x10/2x14 AWG 1x6/2 x 4 mm
2
1x10/2x12 AWG
stranded cable 1x4/2x1.5 mm
2
1x12/2x16 AWG 1x4/2x2.5 mm
2
1x12/2x14 AWG
Wire strip length 7 mm 9 mm
Technical data
VI-2012, www.findernet.com