Data Sheet

1 CO (SPDT)
10/15 A
250/400 V
2,500 VA
500 VA
0.44 kW
10/0.3/0.12 A
300 mW (5 V/5 mA)
AgSnO
2
1 NO (SPST-NO)
0.3 A
24 V
(0.8…1.1)U
N
24 V
24 V
0.6 VA (50 Hz)/0.4 W
(0.8...1.1) U
N
(0.8...1.1) U
N
1,000
–20…+50 °C
IP 20
Contact specification
Contact configuration
Rated current/Maximum peak current I
N
/I
max
Rated voltage/Maximum switching voltage U
N
/U
max
Rated load AC1
Rated load AC15
Single phase motor rating (230 V AC)
Breaking capacity DC1 (24/110/220 V)
Minimum switching load
Standard contact material
Feedback contact specification (terminals B1-B2)
Contact configuration
Maximum current
Rated voltage AC/DC
Supply & Input specification
Nominal voltage U
N
AC (50/60 Hz)
U
N
DC
Rated power P
N
Operating range V AC
V DC
Ambient temperature range
Protection category
19 Series - Override & Status indicating modules
Features
Auto/Off/On output module 10 A
Auto/Off/On output module intended to
permit the automatic control of pumps, blowers
or motor groups. Or, in the case of installation,
maintenance or failure, to permit the load
equipment to be turned “Off“ or controlled
under “On“ control
Ideal interface for PLC and electronic systems
Only 11.2 mm wide
3 function selector switch:
- Auto: works as a monostable relay
(following A3 input)
- Off: relay permanently OFF
- On: relay permanently ON
24V AC/DC supply and module input
35 mm rail (EN 60715) mounting
Application examples:
control of pumps, blowers or motor groups
primarily suited to Industrial control systems
1 CO output contact
11.2 mm wide
Feedback contact
19.21.0.024.0000
Wiring diagram
AUTO
ON
OFF
B1-B2
1
For outline drawing see page 11