Datasheet

4
1 CO (SPDT)
5/15
250/400
1,250
250
0.185
3/0.35/0.2
500 (10/5)
AgCdO
1 NO (SPST-NO)
100/10
24
24
24
1 (50 Hz)/0.6
(0.8…1.1) U
N
(0.8…1.1) U
N
–20…+50
IP20
Output specification (terminals 12-11-14)
Contact configuration
Rated current/Maximum peak current A
Rated voltage/Maximum switching voltageV AC
Rated load AC1 VA
Rated load AC15 (230 V AC) VA
Single phase motor rating (230 V AC) kW
Breaking capacity DC1 (24/110/220 V) A
Minimum switching load mW (V/mA)
Standard contact material
Feedback output specification (terminals 53-54)
Contact configuration
Maximum / Minimum current mA AC/DC
Rated voltage V AC/DC
Supply & Input specification
Nominal voltage (U
N
) V AC (50/60 Hz)
VDC
Rated power VA (50 Hz)/W
Operating range AC
DC
Technical data
Ambient temperature range
Protection category
Approvals (according to type)
19 Series - Override & Status indicating modules
Features
Override module - Auto/Off/Hand
Auto/Off/Hand override module intended to
permit the automatic control of pumps, blowers
or motor groups. Or, in the case of installation,
maintenance or failure, to permit the load
equipment to be turned “Off“ or controlled
under “Hand“ control
3 function selector switch:
- Auto: work as a monostable relay relay
(following A3 input)
- Off: relay output permanently Off
- Hand: relay output permanently On
24V AC/DC supply & input
35 mm rail (EN 60715) mounting
Application examples:
control of pumps, blowers or motor groups
commonly associated with building
management systems
1 CO output contact
1 feedback output contact
17.5 mm wide
LED indicator
19.41.0.024.0000
Wiring diagram
53-54 feed back information to the controller for Auto-operation
A3-A2 Requested operation
For outline drawing see page 11
Controller, PLC Type 19.41
Request
Response
LED Signals
Auto-Operation
Intervention-(Manual-)Operation
Switch position:
VI-2012, www.findernet.com