Datasheet

6
0…10 (Imax 20mA - short-circuit protected)
>2.5 V
> 5 V
>7.5 V
1 NO (SPST-NO)
100 /10
24
24
24
0.9 / 0.7
(0.8…1.1) U
N
(0.8…1.1) U
N
–20…+50 °C
IP20
(0…10)V Signal specification (terminal Y-in)
Input control signal V DC
Green LED 25%
Green LED 50%
Green LED 75%
Feedback output specification (terminals 51-52)
Output configuration
Maximum / Minimum current mA
Rated voltage V AC/DC
Supply & Input specification
Nominal voltage (U
N
) V AC (50/60 Hz)
V DC
Rated power AC/DC VA (50 Hz)/W
Operating range AC
DC
Technical data
Ambient temperature range
Protection category
Approvals (according to type)
19 Series - Override & Status indicating modules
Features
Analogue override module - Auto/Hand
(0…10)V
Analogue output module intended to provide,
by the selection switch on the front panel, a
(0…10) V output, automatically or by hand.
With the selector switch in position “A“
(Automatic) the (0…10) V signal is derived
from the controller.
In position “H” (Hand) the controller signal is
ignored and the (0…10) V signal is derived
directly from the potentiometer setting on the
facia of the module
The level of the (0…10) V output signal is
displayed by 3 green LEDs, set at >25%,
>50% and >75%.
24V AC/DC supply
35 mm rail (EN 60715) mounting
Application examples:
permits the direct control of proportional
valves under exceptional circumstances or
where the automatic controller has failed
Analogue output (0…10)V,
plus 1 feedback output contact
17.5 mm wide
LED indicator
19.50.0.024.0000
Wiring diagram
53-54 feed back information to the controller for Auto-operation
Y
in
-A2 / Hand = Set point (set value) (0…10) V DC;
requested by the controller or manual
For outline drawing see page 11
Controller, PLC Type 19.50
Request
Response
LED Signals
Auto-Operation
Intervention-(Manual-)Operation
Switch position:
VI-2012, www.findernet.com