Datasheet

25A modular contactor - 4 pole
35mm wide
NO contact gap ≥3mm, double break
Continuous duty for the coil and contacts
AC/DC silent coil (with varistor protection)
Protective separation (reinforced insulation)
between coil and contacts
Mechanical and LED indicators as standard
Auto-On-Off selector version available
AgNi and AgSnO
2
contact versions available
Compliant with EN61095:2009
Auxiliary contact module available,
quick-assembly with the main contactor
(1 NO + 1 NC and 2 NO versions)
For railway applications; materials compliant
with fire and smoke characteristics
(EN 45545-2:2013)
35mm rail (EN60715) mount
22.34…1xx0/22.34…4xx0
Screw terminal
22.34.0.xxx.1xx0 22.34.0.xxx.4xx0
* Contact gap ≥3mm for NO
contacts only;
NC contacts ≥1.5mm
AgNi contacts, specifically
intended for resistive and
slightly inductive loads as well
as for motor loads
AgSnO
2
contacts, specifically
intended for lamp loads and
for high inrush current loads
4 NO
(x3x0)
3 NO + 1 NC
(x7x0)
2 NO + 2 NC
(x6x0)
For outline drawings see page 10
Contact specification
Contact configuration 4 NO, 3mm* (or 3NO + 1NC or 2NO + 2NC)
Rated current/Maximum peak current A 25/80 25/120
Rated voltage VAC 250/440 250/440
Rated load AC1/AC-7a (per pole @250V) VA 6250 6250
Rated current AC3/AC-7b A 10 10
Rated load AC15 (per pole @230V) VA 1800 1800
Three-phase motor rating (400 - 440VAC) kW 4 4
Rated load AC5a (per pole @250V) A 15 15
Rated current AC-7c A 10
Nominal lamp rating:
230V incandescent/halogen W 800 2000
fluorescent tubes with
electronic ballast W 300 800
fluorescent tubes with
electromechanical ballast W 200 500
CFL W 100 200
230V LED W 100 200
LV halogen or LED with
electronic ballast W 100 200
LV halogen or LED with
electromechanical ballast W 300 800
Breaking capacity DC1: 30/110/220V A 25/5/1 25/5/1
Minimum switching load mW (V/mA) 1000 (10/10) 1000 (10/10)
Contact material AgNi AgSnO
2
Coil specification
Nominal voltage (U
N
) VDC/AC (50/60Hz) 12 - 24 - 48 - 60 - 120 - 230 12 - 24 - 48 - 60 - 120 - 230
Rated power AC/DC VA (50Hz)/W 2/2.2 2/2.2
Operating range DC/AC (50/60Hz) (0.8…1.1)U
N
(0.8…1.1)U
N
Holding voltage DC/AC (50/60Hz) 0.4 U
N
0.4U
N
Must drop-out voltage DC/AC (50/60Hz) 0.1U
N
0.1U
N
Technical data
Mechanical life AC/DC cycles 2·10
6
2·10
6
Electrical life at rated load AC-7a cycles 150·10
3
30·10
3
Operate/release time ms 18/40 18/40
Insulation between coil
and contacts (1.2/50µs) kV 6 6
Ambient temperature range °C –20…+50 –20…+50
Protection category IP 20 IP 20
Approvals (according to type)
4
VII-2018, www.findernet.com
L
22 SERIES
Modular contactors 25- 40- 63A
22
SERIES